System Set-Up
• DHW time setting
Determine following time duration : operation time of DHW tank heating, stop time of DHW tank
heating, and delay time of DHW tank heater operating.
- Active time : This time duration defines how long time DHW tank heating can be continued.
- Stop time : This time duration defines how long time DHW tank heating can be stopped. It is also
regarded as time gap between DHW tank heating cycle.
• TH on/off Variable, heating air
Setting Thermal on/off Air Temperature gap in heating mode
0
1
2
3
• TH on/off Variable, heating water
Setting Thermal on/off Water Temperature gap in heating mode
0
1
2
3
• TH on/off Variable, cooling air
Setting the step value to adjust air temperature gap in cooling mode
0
1
2
3
• TH on/off Variable, cooling water
Setting the step value to adjust water temperature gap in cooling mode
0
1
2
3
70 Hydro Kit
Th On
-0.5 ℃
-1 ℃
-2 ℃
-3 ℃
Th On
-2 ℃
-3 ℃
-4 ℃
-1 ℃
Th On
0.5 ℃
1 ℃
2 ℃
3 ℃
Th On
0.5 ℃
1 ℃
2 ℃
3 ℃
Th Off
1.5 ℃
2 ℃
3 ℃
4 ℃
Th Off
2 ℃
3 ℃
4 ℃
1 ℃
Th Off
-0.5 ℃
-1 ℃
-2 ℃
-3 ℃
Th Off
-0.5 ℃
-1 ℃
-2 ℃
-3 ℃