2Way Valve - LG Hydro Kit Installation Manual

Air-to-water
Hide thumbs Also See for Hydro Kit:
Table of Contents

Advertisement

Accessories Installation

2Way Valve

2way valve is required to control water flow while cooling operation. Role of 2way valve is to cut off
water flow into under floor loop in cooling mode when fan coil unit is equipped for cooling operation.
General Information
supports following 2way valve.
Hydro Kit
Type
NO 2-wire(1)
NC 2-wire(2)
(1) : Normal Open type. When electric power is NOT supplied, the valve is open.
(When electric power is supplied, the valve is closed.)
(2) : Normal Closed type. When electric power is NOT supplied, the valve is closed.
(When electric power is supplied, the valve is open.)
How to Wire 2Way Valve
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the indoor unit and open the control box.
Step 2. Find terminal block and connect wire as below.
2WAY VALVE
(A)
14
15
16
L1
L2
N
BR
WH
BL
(NO)
(NC)
(N)
2way valve
(NO) : Live signal (for Normal Open type) from PCB to 2way valve
(NC) : Live signal (for Normal Closed type) from PCB to 2way valve
(N) : Neutral signal from PCB to 2way valve
Final Check
• Flow direction :
- Water should not flow into under floor loop in cooling mode.
- To verify the flow direction, check temperature at the water inlet of the under floor loop.
- If correctly wired, this temperatures should not be approached to 6 °C(42 °F) in cooling mode.
46 Hydro Kit
Power
Operating Mode
Closing water flow
230 V AC
Opening water flow
Closing water flow
230 V AC
Opening water flow
!
CAUTION
Dew Condensation
• Wrong wiring can yield dew condensation on the floor. If radiator is
connected at the under floor water loop, dew condensation can be
occurred on the surface of the radiator.
!
WARNING
Wiring
• Normal Open type should be connected to wire (NO) and wire (N) for
valve closing in cooling mode.
Supported
Yes
Yes
Yes
Yes

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hydro kit arnh08gk3a4

Table of Contents