System Set-Up
NOTICE
Emergency Operation
• Definition of terms
- Trouble : a problem which can stop system operation, and can be resumed temporally under
limited operation without certificated professional's assist.
- Error : problem which can stop system operation, and can be resumed ONLY after certificated
professional's check.
- Emergency mode : temporary heating operation while system met Trouble.
• Objective of introducing 'Trouble'
- Not like airconditioning product, Air-to-Water heat pump is generally operation in whole winter
season without any system stopping.
- If system found some problem, which is not critical to system operating for yielding heating
energy, the system can temporarily continue in emergency mode operation with end user's
decision.
• Classified Trouble
- Trouble is classified two levels according to the seriousness of the problem : Slight Trouble and
Heavy trouble
- Slight Trouble : a problem is found inside the unit. In most case, this trouble is concerned with
sensor problems. The outdoor unit is operating under emergency mode operation condition
which is configured by DIP switch No. 4 of the unit PCB.
- Heavy trouble : a problem is found inside the outdoor unit. As the outdoor unit has problem, the
emergency mode operation is performed by electric heater located in the unit.
- Option Trouble : a problem is found for option operation such as water tank heating. In this
trouble, the troubled option is assumed as if it is not installed at the system.
• When the AWHP has any trouble,
(1) If there is not a function to judge possibility of operation :
Once an error occurs mainly in indoor unit, AWHP stops. On the other hand, Remocon allows
the product to activate On/ Off operation. (On : emergency operation)
- Slight / Heavy trouble : Heating Operable only
- Critical trouble : Full stop
- Treatment priority : Critical>Heavy>Slight
(2) If there is a function to judge possibility of operation :
Depending on the status of slight / heavy / critical trouble, pop-up phrase is guided separately
on display.
- Slight trouble : Heating/Cooling Operable
- Heavy trouble : Heating Operable only
- Critical trouble : Service center request
AWHP operates when user pressed OK button on pop-up window.
58 Hydro Kit