• Every six months (record all readings)
- Measure the battery string voltage. If necessary, adjust the float
voltage to the correct value.
- Measure individual bloc voltages.
- Bloc to bloc connection resistance (Ohms)
- Terminal Connection Resistance (Ohms)
- Ambient temperature in the immediate environment
Inspect for contamination by dust, lose or corroded connections. If
necessary, isolate the string/bloc and clean with a damp soft cloth.
Warning: Do NOT use any type of oil, solvent, detergent,
petroleum-based solvent or ammonia solution to clean the battery
containers or lids. These materials will cause permanent damage to
the battery container and lid and will invalidate the warranty.
Keep a logbook to record values, power outages, discharge tests,
etc.
An autonomy check can be carried out once or twice a year.
The above record taking is the absolute minimum to protect the
warranty.
This data will be required for any warranty claim made on the
battery.
Contact EnerSys
if you have any questions regarding
®
maintenance.
7. Disposal
HX + batteries are recyclable. Scrap batteries must
DataSafe
®
be packaged and transported in accordance with prevailing
transportation rules and regulations.
Scrap batteries must be disposed of in compliance with local and
national laws by a licensed or certified lead acid battery.
EnerSys World Headquarters
2366 Bernville Road, Reading
PA 19605, USA
Tel: +1-610-208-1991 /
+1-800-538-3627
© 2018 EnerSys. All rights reserved. Trademarks and logos are the property of EnerSys and its affiliates unless otherwise noted.
EnerSys EMEA
EnerSys Asia
EH Europe GmbH
152 Beach Road
Baarerstrasse 18
Gateway East Building #11-03
6300 Zug, Switzerland
Singapore 189721
Tel: +65 6508 1780
Contact
Need help?
Do you have a question about the DataSafe HX+ and is the answer not in the manual?
Questions and answers