The High Bay Luminaire is ideal for installations with mounting heights over 25 feet.
The fixture can be mounted with a hook or pendant with flexible adjustments to create
uniform light from fixture to fixture.
WARNING:
This product must be installed in accordance with applicable local, state, and national electrical
codes by a licensed person familiar with the construction and operation of the product and
hazards involved.
This luminaire must be adequately grounded for protection against shock hazards and to assure
proper operation.
Disconnect power before servicing.
Suspend from adequate structure that can safely support the fixture.
MIN 90°C SUPPLY CONDUCTORS
Do not operate in ambient temperatures above those indicated on the luminaire Label.
Make sure the supply voltage is within the voltage range stated on the Label
Use only UL or IEC approved wire for input/output connections. Minimum size 18 AWG
General :Provide at least 12"of clearance from the top of the fixture to any ceiling or surface above.
HOOK MOUNT INSTALLATION:
1. To pre-assemble hook and hub. Make sure to fix anti-rotation M4 screw
High Bay Luminaire Series
1
INSTALLATION INSTRUCTIONS

Advertisement

loading

Summary of Contents for Delta High Bay Luminaire Series

  • Page 1 High Bay Luminaire Series INSTALLATION INSTRUCTIONS The High Bay Luminaire is ideal for installations with mounting heights over 25 feet. The fixture can be mounted with a hook or pendant with flexible adjustments to create uniform light from fixture to fixture.
  • Page 2 2. The Weight of High Bay fixture is approximately 19.8 lb. Please ensure the structure and the suspending cable/chain are suitable for the weight of the fixture. 3. To make electrical connections, attach the lead wires according to the colors below. ...
  • Page 3: Pendant Mount Installation

    PENDANT MOUNT INSTALLATION: The fixture mounting receiver is threaded for 3/4” NPT pipe. 1. Feed the power cable through the conduit, and into the junction box. Attach the fixture to the conduit. 2. Insert set screw in order to secure the fixture to the Pipe.
  • Page 4 3. The fixture should already be factory set for correct balance and orientation. If adjusting balance or orientation is necessary, make corrections using the adjustment screws in the locations shown Adjustment screws 4. Make wire connections inside the junction box according to the following color wires : ...
  • Page 5: Wall Mount Installation

    WALL MOUNT INSTALLATION 1. To pre-assembled bracket and luminarie .Use screw and washer to fix the luminaire on the structure. Suggest to use 3/8” (M10) Screw and T 2.0 min washer. bracket 2. Loosen the M10 and M4 screw, and tilt the luminaire to the determinded direction. If determinded, fixed the Screw Torque Suggestion: M10: 18 ft-lbs (245 Kgf.cm)
  • Page 6 AIRCRAFT CABLE INSTALLATION: 1. Aircraft cable assemblies to the luminaire with two aircraft cable assembly as shown below Notes: a. The assembly location must be shown below b. Do not exceeded angle greater than a 30° between the cables and the gravity line 30 deg Max...
  • Page 7: Safety Cable Installation

    2. Connect power cable conductors as follows:  Green wire connects to Safety Ground.  White wire connects to Neutral  Black wire connects to Live SAFETY CABLE INSTALLATION: 1.Attach one end of the safety cable through the hole between the fin on the luminarie 3.
  • Page 8 1~10V DIMMING WIRING INSTRUCTION DB series of high bay fixtures come standard with 1-10V dimming interface. The dimming is controlled by 1~10VDC dimming signal (to be provided by other devices). An 8 to 10V DC signal will have about 100% lumen output. A 0 to 1V DC signal will have about 10% lumen output.