Important Information and Safety Tips
Only experienced personnel should connect the ProI/O to
other systems that comply with required safety regulations.
External power sources connected to the ProI/O must not
exceed the maximum allowable voltage (24V) and must be
protected accordingly. In addition, correct polarity must be
utilized to avoid damage to the ProI/O. Failure to do so will void
the warranty and Weigl Works, LLC or Weigl will not be liable for
any resulting damages.
When connecting solenoids, a freewheeling diode for each
solenoid is required. They should be mounted as close as
possible to the solenoid. Please refer to the wiring diagram in the
manual. If this is not observed, the output driver will be
destroyed and will void the warranty.
The ProI/O should not be exposed to extreme heat or
humidity before, during or after installation. If the device is used
for outdoor installations, it must be protected with proper
weather proofing enclosures. Direct sunlight may also lead to
overheating.
Damages caused by improper handling, improper wiring or
improper use will void warranty and Weigl Works, LLC or Weigl-

1.1 FCC and CE Compliance

EM will not be held liable.
Weigl ProI/O's which are hardware revision 1.10 or later have
been tested to comply with FCC and CE requirements.