Download Print this page

Voltage Regulation - Tripp Lite Smart Pro SM3000NAFTA Specifications

Interactive ups system - nafta assembled version of smart3000net

Advertisement

UPS input connection
type
UPS Input cord length
(ft.)
UPS Input cord length
(m)
Recommended
Electrical Service
Input cord length (m)
BATTERY
Full load runtime
(minutes)
Half load runtime
(minutes)
External battery pack
compatibility
DC system voltage
(VDC)
Battery recharge rate
(included batteries)

VOLTAGE REGULATION

Voltage regulation
description
Overvoltage correction
Undervoltage correction
Severe undervoltage
correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
UPS AC suppression
response time
EMI / RFI AC noise
suppression
PHYSICAL
Installation form factors
supported with included
accessories
Primary form factor
L5-30P
8
2.4
30A 120V
2.4
7 min. (2400w)
23 min. (1200w)
BP24V28-2U
(limit 1);
BP24V70-3U
24
Less than 9 hours from 10% to 90%
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 87 to 140
Input voltages between 127 and 140 are reduced by 12%
Input voltages between 95 and 105 are boosted by 10%
Input voltages between 87 and 94 are boosted by 22%
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible alarm indicates power-failure, overload and low-battery conditions
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
2 Switches control off/on power status and alarm-cancel/self-test operation; set of 4 rear-panel switches control
system enable and contact closure port inverter shutoff commands
480
Instantaneous
Yes
Tower
Tower
(multi-pack compatible)

Advertisement