Download Print this page

IDEC SX5A Series Communication Interface Manual

As-interface (communication terminal and repeater)

Advertisement

Quick Links

Communication & Networking
SX5A AS-Interface (Communication Terminal and Repeater)
AS-Interface Communication Terminals (Slave Modules)
IP67 I/O Module
AS-Interface Ver. 2.1 compliant, capable of connecting 62 slaves
Compatible with 2- and 3-wire sensors
With AS-Interface power and input status indicators
Overload detection function on the sensor power supply
Output overload detection function (2 in/2 out model, 4 in/3 out model)
IP20 Terminal Block
AS-Interface Ver. 2.1 compliant, capable of connecting 62 slaves
Removable terminal blocks
Compatible with 2- and 3-wire sensors
AS-Interface power and input status indicators
IEC62026-2 compliant
Repeater
No address setting required.
The AS-Interface network can be extended up to 300 m.
IP65 protection
Easy connection to AS-Interface fl at cables.
SX5A AS-Interface Communication Terminals
IP67 I/O
Module
IP20 I/O
Terminal Block
Module
Base Modules
Base Module for IP67
I/O Module
Repeater
Description
A repeater can extend the AS-Interface Network up
to 300m.
I/O Specifi cations
Terminal
Input Points
4
4
Connector
2
4
4
4
4
Applicable I/O Module
4 in model
2 in/2 out model
4 in/3 out model
SX5A-RP1
USA: 800-262-IDEC
Part Numbers
Input
Output Points
Output
NPN
PNP
PNP
2
PNP
PNP
3
PNP
NPN
PNP
PNP
3
PNP
Description
Substructure module to connect to AS-Interface
fl at cables for AS-Interface bus and auxiliary power
Part Number
Canada: 888-317-IDEC
SX5A AS-Interface
Applicable Base Module
Part Numbers
(order separately)
SX5A-SWN40S02
SX5A-B3FF
SX5A-SWN40K02N
SX5A-B3FF
SX5A-SWM22KS2N
SX5A-B3FF
SX5A-SWM43KS2N
SX5A-B2FF
SX5A-SSN40S0N
SX5A-SSN40K0N
SX5A-SSM43KSN
Part Numbers
SX5A-B3FF
SX5A-B2FF
255

Advertisement

loading

Summary of Contents for IDEC SX5A Series

  • Page 1 Substructure module to connect to AS-Interface I/O Module fl at cables for AS-Interface bus and auxiliary power 4 in/3 out model SX5A-B2FF Repeater Description Part Number A repeater can extend the AS-Interface Network up SX5A-RP1 to 300m. USA: 800-262-IDEC Canada: 888-317-IDEC...
  • Page 2 Branch AS-Interface fl at cable M12 Branch Connector SX9Z-CT1 to M12 cables AS-Interface Flat Cable Protect the end of AS-Interface cable SX9Z-CPA1 Degree of protection: IP65 End Tube Ensure IP67 protection on Protection Cap SX9Z-CAP1 unused M12 I/O plugs www.idec.com...
  • Page 3 Standard slave A/B slave Profi le — Communication Data Bits Input Output Input Output Input Output Input Output — — — OUT1 OUT1 — — — OUT2 OUT2 — — — OUT3 — — — — USA: 800-262-IDEC Canada: 888-317-IDEC...
  • Page 4 ADR1N) to the addressing port on the I/O module using the programming device cable (SX9Z-CN1), then the I/O module Assignment stops communication through the AS-Interface line. Change slave addresses using the programming device. Certifi cation AS-International Association Standards UL/c-UL, CE www.idec.com...
  • Page 5: Specifications

    2A max. (OUT1), 1A max. (OUT2, OUT3), 4A total (Tb ≤ 60°C) Communication Error — Output turns off Slave Type A/B slaves Profi le Communication Data Bits Input Output Input Output — OUT1 — OUT2 — OUT3 — — USA: 800-262-IDEC Canada: 888-317-IDEC...
  • Page 6 Connect the hand-held programming device (SX9Z-ADR1N) to the addressing port on the I/O module using the program- Address Addressing Method ming device cable (SX9Z-CN1), then the I/O module stops communication through the AS-Interface line. Change slave Assignment addresses using the programming device. Certifi cation AS-International Association Standards UL/c-UL, CE www.idec.com...
  • Page 7 4 inputs IN1...IN4 AS-i– AS-i+ AS-i– output output output output sensor sensor sensor sensor I– I– AS-i+ For 3-wire sensor For 3-wire sensor For 3-wire sensor For 3-wire sensor 3 outputs O1...O3 FAULT Load AUX+ FAULT AUX– USA: 800-262-IDEC Canada: 888-317-IDEC...
  • Page 8 Pull upper part until STOP. input power is supplied from outside, the INT LED remains off. I/O statuses are indicated on the front LED indicators 3. Set switch INT: sensor supply from AS-Interface EXT: external sensor supply Switching the input power supply INT/EXT www.idec.com...
  • Page 9 Communication & Networking SX5A AS-Interface Dimensions SX5A-SWN40S02 SX5A-SWN40K02N SX5A-SWM22KS2N SX5A-SWM43KS2N Base module is separately ordered Base module is separately ordered 73.5 34.5 73.5 34.5 SX5A-B3FF SX5A-B2FF 77.5 77.5 SX5A-SSN40S0N SX5A-SSN40K0N SX5A-SSM43KSN 22.5 102.3 All dimensions in mm. USA: 800-262-IDEC Canada: 888-317-IDEC...
  • Page 10: Mounting Hole Layout

    Remote I/O Remote I/O Remote I/O Repeater Repeater AS-Interface Cable 1 AS-Interface Cable 2 AS-Interface AS-Interface AS-Interface Power Supply Power Supply Power Supply 100 m max. 100 m max. 100 m max. All dimensions in mm. 300 m max. www.idec.com...
  • Page 11 Hand-held programming device Attach the addressing port adapter to the programming device cable and insert the addressing port adapter into the addressing port on the communication block. USA: 800-262-IDEC Canada: 888-317-IDEC...
  • Page 12 –25 to +85°C (no freezing) Degree of Protection IP20 Weight Approx. 275g Communication Specifi cations AS-Interface Version 2.1 Operation Slave address assignment and data read/write (compatible with the 62-slave mode) Connection Connects to a slave using programming device cable www.idec.com...