olympia electronics BAU LIGHT Series Manual page 2

Self testing maintained emergency luminaires

Advertisement

Automatic Autonomy Test
The Automatic Autonomy Test measures the
device's back up operation and emergency
duration. This test is conducted automatically
every 6 months. In order to be performed, the
mains power supply and the battery should be
connected and fully charged. If the battery is not
fully charged, the test is postponed until the
battery is completely charged. If during this test,
the autonomy is less than nominal, the battery
fault led turns on continuously and the battery
must be replaced. The test lasts for the selected
autonomy.
Emergency Operation
The autonomy duration of battery during
emergency mode is at least the selected
autonomy duration. During emergency mode, a
light source test is also performed.
Wireless communication
The luminaire models have the ability to
communicate over the air with Olympia's control
panels for wireless emergency luminaires. The
luminaires can also communicate with a
PC/laptop through a gateway (Ethernet, Wi-Fi,
USB). For more information, please refert to
Wireless Emergency Lighting guides, available
on the company's website.
Resetting Errors
Hold the A-1900 card in TEST position for 10 to
15 seconds in order to delete all LED indicated
errors. Then
the device enters regular
operation mode.
Indication LED status (with connected mains
power supply).
Charge (Green LED)
On: Good charge condition.
Blink: Battery is charging.
Οff: No battery (No charging current
or disconnected battery).
Fault (Red LED)
Οn : Faulty LED strip (must be replaced) or
emergency
circuit
authorized personnel).
Blink (With Charge LED ON): Autonomy or
low battery problem (the battery must be
replaced).
Οff: No fault.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only.
2. The device must be connected to the mains
Page 2 from 5
(must
be
checked
power supply through a fuse dependent by the
total amount of the line's power load.
3. In case of inactive use for a period greater
than 2 months, disconnect the battery by pulling
out the battery's connector.
4. I
t i
s not allowed to discard batteries into
common trash bins, they must be
discarded only
points. Do not incinerate.
Test and Faults Reset operations with the A-
1900 card (not included and available after
request). For lights test, you must place the
card in front of the TEST indicator and remove it
immediately. For Autonomy Test, you must place
the card in front of TEST and hold it for 5 to 10
seconds.
To reset errors you must place the card in front
of TEST by holding it for 10 to 15 seconds and
removing it.
Only for models GR-750/ST/HP/LL/WL and
GR-752/ST/HP/HL/WL
*15m: When the luminary is installed on a wall.
**17m: When luminary is installed on the ceiling.
The selection must be done while the
luminaire is disconnected from AC and battery
supplies. The selection is achieved through
Switches 2 & 3 of DS1. Switch 1 is not used.
1
2
3
by
1
2
3
1
2
3
in battery recycling
TEST
GR-753/ST/LP/HL/WL
220-240V
INDICATORS
RATED POWER: 4.6W/4.8VA
A-1900
GREEN:CHARGE
BATTERY:3.6V/3Ah
LUMINOSITY: 300lm
RED:FAULT
X 1 A F
1h
4
3h
(default position)
4
8h
4
923753004_09_001
/50-60Hz
IP54
t 40ºC
a
1
8
0
t 5-40ºC MADE IN GREECE