"BAU LIGHT" SERIES SELF TESTING MAINTAINED EMERGENCY LUMINARIES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Cd)
Tx/Rx frequency range
Tx power
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMY DURATION
ILLUMINATION SOURCE
LUMINOUS FLUX (230V AC)
LUMINOUS FLUX (emergency)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
VEWING DISTANCE
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
Each luminaire must be permanently connected
to mains power supply. In normal operation the
illumination LEDs are lit as well as the green
indicating charge LEDs when the battery is
charging. In case of a mains power supply
failure, the luminaire
mode and will light automatically. When the
mains power supply is restored the device turns
to normal operation.
AUTONOMY DURATION SELECTION
The user can select one of the 3 available
minimum autonomy durations 1 hour, 3 hours
and 8 hours. The procedure of autonomy
selection is described on page 2.
TECHNICAL LABEL INSTALLATION
Two additional labels are included in the
package. One for 1 hour duration (60) and one
for 8 hour duration (480). Depending on the
selected duration, the installer must replace the
default 3 hour (180) label with one that has the
required duration. Please take notice of the
orientation of the label.
Page 1 from 5
GR-750/ST/HP/LL/WL GR-751/ST/LP/LL/WL GR-752/ST/HP/HL/WL GR-753/ST/LP/HL/WL
1 h : 300lm / 3 h : 150lm / 8 h : 30lm
EN 62311, EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2,
ΕΝ 61000-3-3, ETSI EN 303 446-1 v1.1.0, ETSI EN 300 220-2 v3.1.1
*15m, **17m
358 x 125 x 88 mm 358 x 85 x 88 mm 358 x 125 x 88 mm
787gr.
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
enters in emergency
(for LED MODULE specifications see page 4)
220-240V AC/50-60Hz
4.1W / 4.3VA
3.6V/1.5Ah
868 - 870MHz
11dBm
LED Charge, Battery Fault LED / Magnetic Test Contact
24 h
1 h / 3 h / 8 h manually selected (default 3h)
30 white LED
270lm
IP54
5 to 40 C
up to 95%
15m
ABS/PC, PC
756gr.
3 years (1 year for the battery)
Battery Charging
The battery charging procedure is controlled by
the processor, this maintaining its best possible
preservation, as it extends its duration.
Battery Cut-off
The luminaire enters this mode when the mains
power supply fails and battery has lost all its
energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Manual Test
This test can be done by using the A-1900 card
as described on page 2. The light source and
the emergency circuit of the device are tested.
The manual test can be conducted only if the
mains power supply and the battery are
connected. This test lasts for 3 seconds.
Automatic Operational Test
This test includes all the operations of the
manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected. This test lasts for 3 seconds.
4.5W / 4.7VA
3.6V/3Ah
1 h : 350lm / 3 h : 280lm / 8 h : 90lm
o
*15m, **17m
15m
358 x 85 x 88 mm
859gr.
824gr.