60 Parameter settings
Index
Name
SBC usage
SBC.15
SSE/SS1 SBC
speed
1) With the FPTC module, the recommended value is Immediate STO, but
other safety functions in the FSO module can require that the value is
Emergency ramp. With both settings, the FSO module always activates the
drive STO function immediately in motor overtemperature situations (SMT
function activated).

FSE module and safety pulse encoder parameters

Set these parameters only when you use a safety pulse encoder and
the FSE-31 pulse encoder interface module with the FSO-21 module.
Index
Name
200.231
FSE 3X act
and par version
200.232
Number of en-
coders
S_ENC-
Safe pulse en-
GEN.01
coder version
S_ENC-
FSE diagnostic
GEN.11
failure reaction
Example
Description
value
0.0 rpm
Sets the absolute speed below which
the FSO module activates the brake
(SBC) while ramping.
0.0 rpm: The feature is not in use.
In the safety functions described in this
manual, this feature is not used. Make
sure that the value is 0.0 rpm.
Example
Description
value
Version 1
Activates the FSE-31 encoder interface
and shows the version of the encoder
parameter groups (91 and 92).
Single en-
Shows the number of safety pulse en-
coder CH1
coders connected to the FSE module.
Version 1
Activates the safety pulse encoder and
shows the version parameter group
S_ENCGEN.
STO
Sets the action taken when there is a
problem with the FSE module.
STO: The FSO module goes into the
Fail-safe mode and activates the drive
STO function.
Note: This parameter is relevant only
when there are no active safety func-
tions.