Model: FDEN series
Fan motor
● Change by the jumper wire
Name
With
Input signal - Reverse invalid
J1 (SW7-1)
(1)
None
Input signal - Run stop
With
Heating thermostat OFF-Lo
J2 (SW7-2)
(1)
None
Heating thermostat OFF-Stop, Lo
With
Normal operation operable
J3 (SW7-3)
(1)
None
Operation permission prohibited
With
Normal
J4 (SW7-4)
(1)
None
Heating temp. +3
With
Louver free stop control - Invalid
J5 (SW8-1)
(1)
None
Louver free stop control - Effective
With
Freeze prevention fan control activated.
J6 (SW8-2)
(1)
None
Freeze prevention fan control deactivated.
Note (1)
"None" means that jumper wire is not provided on the PCB or the
connection is cut
(2)
The replacement board is not equipped with jumpers J1 ~ J6. Instead,
SW7 and 8, with the same functions as jumpers J1~J6, are used in the
position where the jumpers were previously. Set SW7 and 8 locally in
accordance with the above table.
PCB power supply connector
(Primary side)
Power supply
L2
CNW1
CNW0
CNM1
L1
C57
CNQ
CNT
Connector
(CNT)
Heat exchanger thermistor,
Return air thermistor
(Thl-R1, Thl-A)
Function
IC7
CNE
SW2
SW5
SW10
CNH CNN1
Address switch
(SW2)
Heat exchanger thermistor
(Thl-R2)
● Control change switch (SW5, SW9, SW10)
Function of DIP switch SW5 (Usually all turned OFF)
Switch
ON
SW5-3
SW5-4
OFF
Function of DIP switch SW9 (Usually all turned OFF)
Switch
SW9-3
SW9-4
Note (1) It is normally ON only in the case of SW9-4.
Function of DIP switch SW10 (Usually all turned OFF)
Switch
SW10-1 (J9)
OFF
SW10-2
SW10-3
(J10)
(J11)
ON
131
-
-
PCB power supply
connector
IC8
(Secondary side)
Remote controller
DIP switch
(SW5)
SW8
J5, J6
SW9
SW7
(SW8)
J1~J4
(SW7)
DIP switch
(SW9)
J9~J11
(SW10)
Function
Setting time : 1000hrs. (Unit stop)
ON
Setting time : 1000hrs. (Display)
OFF
Setting time : 600hrs. (Display)
ON
OFF
Setting time : 180hrs. (when shipped from factory)
Function
Emergency operation
ON
OFF
Normal
ON
Fan control : Powerful mode
OFF
Fan control : Mild mode
Function
Auto swing function - None
OFF
Auto swing function - With
ON
Remote controller air flow –
OFF
ON
Remote controller air flow 1 speed
OFF
Remote controller air flow 2 speed
ON
Remote controller air flow 3 speed