Installation
34
D
2
NOTE
The N (neutral) hole in the contact carrier must be connected to the N(neutral) terminal
of the AC circuit breaker on the distribution box correctly. Otherwise the product could be
damaged seriously.
The PE (Protective Earth) grounding connector in the contact carrier must be connected
to the 6 (Grounding) terminal of the distribution box correctly. Otherwise the product
could be damaged seriously.
E
Connect the wires to the corresponding
wire holes on the contact carriers.
Wire hole 1
Grid wire L1
Wire hole 2
Grid wire L2
Wire hole 3
Grid wire L3
Wire hole N
Grid wire N
Wire hole 6
Grounding wire PE
And then fasten the screws on the
cantact carriers. (1 N.m)
Push the contact carriers into the housing
until it clicks.