4.6 m
o u n t i n G
– Install the head-end station vibration-free.
Avoid, for example, mounting the head-end station onto a lift shaft or any
other wall or floor construction that vibrates in a similar way.
– To avoid too strong heating of the head-end stations it is not admissible
to mount them one upon the other without using thermic precautions (e.g.
permanently air recirculation, ventilation, heat deflectors etc.).
– Using the supplied mounting brackets, the head-end station can be mounted
to a wall, upright standing, or in a 19" cabinet. Before proceeding, ensure
that the minimum distance requirements (500 mm above/below and 75
mm behind the device at wall mounting / 500 mm above and 75 mm be-
low/behind the device at upright mounting / 200 mm above/below and
100 mm behind the device at mounting in a 19" cabinet) will be met.
– If mounting to a wall or on a shelf, ensure that ...
- The wall or the shelf can support the weight of the head-end station
- There is adequate air conditioning
- The permissible ambient temperature will be maintained
– If mounting inside a 19" cabinet, ensure that ...
- there is adequate air conditioning.
- the permissible ambient temperature will be maintained.
- the mounting rack in the cabinet can support the weight of the head-end
station.
Note:
To maintain an ambient temperature of < 50 °C, use an additional fan or a
safety temperature limiter with reclosing interlock if necessary.
+ 12 V / 1 A
Fig. 12: Power supply for additional fan