COMMISSIONING FLOWCHART Characteristics correspond Check characteritics Page 1-8 to product code Mounting DIN Rail Page 2-3 Bulkhead Mounting Page 2-4 Wiring Power Page 2-7 Control Page 2-8,2-9,2-10 Applying the control signal Page 2-9 ANA terminal Block If External Power Supply Auxiliary Power Supply Page 2-10 (for electonics od/and fan)
Page 4
.........6-1 Eurotherm worlwide sales and services ... . .7-1 PURPOSE OF MANUAL This manual ( Issue 3.0 ) describes the Basic Version and all Options...
Page 5
Conducted at radiofrequencies ‘Burst mode’ and ‘Single-cycle’ CISPR 11 Class A group 2 Table 2. EMC emissions standards compliance EMC GUIDE To help you deal with installation-dependent electromagnetic interference effects,Eurotherm provides an ‘Electromagnetic compatibility’ installation guide (ref. HA 025464 ENG) which CE CONFORMITY DECLARATION sets out best current practice regarding EMC.
Page 6
Identification 1. Chapter 1 POWER THYRISTOR UNIT IDENTIFICATION Contents Page 1.1. General presentation ........1-2 1.2.
Page 7
Identification 1. Chapter 1 IDENTIFICATION 1.1. GENERAL PRESENTATION A 7200A series thyristor unit comprise of two channel, controlled by thyristors. 7200A series thyristor units are used to control the electrical power of three-phase industrial loads ; such as : Low coefficient resistive loads Short wave infrared elements for units with a rating ≤...
Page 8
Identification Protective earth Power terminals terminal (supply) Internal power wiring diagram DLF option : Diagnostic alarm Electronics supply Zero crossing firing mode : Firing request LED Control terminal pinouts Control connector Power terminals (load) Figure 1-2 General view of a 7200A power unit ratings from 80 A to 100 A 7200A User Manual...
Page 9
Identification Figure 1-3 General view of a 7200A power unit ≥ 125 A rating 7200A User Manual...
Page 10
Identification 1.2. TECHNICAL SPECIFICATIONS 1.2.1 Use Thyristor unit, variant 4 (see Standard EN 60947-4-3) 1.2.2. Power for uninterrupted service. Nominal current per phase 16 A to 200 A at 45 °C (see product code) Nominal line to line voltage 200 V to 500 V (see code). Frequency Use from 47 to 63 Hz (automatic matching) Dissipated power...
Page 11
Identification 1.2.6. Firing modes Zero crossing firing • ‘Burst mode’, base time : 16 or 64 cycles 1.2.7. Control • ‘Single-cycle’, base time : 1 cycle Parameters • Standard (on balanced three-phase supply) : Load voltage squared (V Linearity and Stability Better than ±2% of full scale (on balanced three-phase supply) 1.2.8.
Page 12
RH from 5% to 95% non-condensing, non-streaming. Over-Voltage Over-voltage category II (as defined by IEC 60664) Eurotherm’s policy of continuous product improvement and development means that the specifications in this document may be modified without prior notice. 7200A User Manual...
Page 13
Identification 1.3. Codification Ratings 1. Nominal current per phase Code 9. Manual language Code 16 amps French 25 amps English 40 amps German * 63 amps 80 amps 10. Selected options Code 100 amps 100A 125 amps 125A Without options: V control and NONE 160 amps...
Installation 2. Chapter 2 INSTALLATION 2.1. SAFETY DURING INSTALLATION (MOUNTING AND WIRING) Danger! • 7200A power thyristor units must be installed and wired by qualified staff authorised to work on low voltage industrial electrical facilities. • Units must be installed in a fan-cooled cabinet, to ensure that condensation and pollution are excluded, with a class of at least 2 according to IEC 60664.
Installation 2.2. MOUNTING 2.2.1. TYPES OF MOUNTING • DIN rail mounting and bulkhead mounting - 16 A to 63 A only • Bulkhead mounting with screws ≥ 80 A DIN rail mounting (≤ 63 A only) Bulkhead mounting Attachment plate DIN rail Attachment plate Screws...
Installation 2.2.4. BULKHEAD MOUNTING For 2 M4 screws For 2 M6 screws For 2 M4 screws Figure 2-2 Bulkhead mounting - 16 A to 63 A units For 2 M6 screws For 2 M6 screws Figure 2-4 Bulkhead mounting - ≥ 125 A units For 2 M6 screws Figure 2-3 Bulkhead mounting - 80 A to 100 A units...
(independently of the three-phase load configuration) and control connectors. To supply network Protection and cut)out installed by user Thyristor fuses (External ≤ 100 A) Protective Earth ε EUROTHERM 7200 63 A / 500 V 1/L1 3/L2 5/L3 2/T1 4/T2 6/T3...
Page 19
Installation Supply protection and cut-out. Installed by user Controlled channel terminal (supply side) Protective earth terminal Internal fuse compartment (thyristor protection) Internal power wiring diagram Controlled channel terminal (load side) 2/T1 4/T2 Internal fuse blown contact(MSFU) Figure 2-6 General connection diagram for units with rating ≥ 125 A 7200A User Manual...
Installation 2.3.3. CONTROL CONNECTIONS Terminal blocks on the underside of the 7200A power thyristor unit are used to connect: • the control signals (analogue) • the auxiliary or electronics supply and the neutral • alarm relay and acknowledgement contacts 2.3.3.1.Control terminal blocks The wires used should be stripped for a length of 6 to 7 mm.
100% +5 V internal a) external signal, e.g. from b) manual command from Eurotherm series 2000 controller external potentiometer Figure 2-8 Control signal connection (self-powered unit, base version) The analogue control signal terminal block is labelled ANA.IN. The input available corresponds to the input type selected in the product code (specified range of voltage or current).
Protection / Cut-off installed by user Supply Network ε EUROTHERM 7200 63 A / 500 V EN 60947-4-3 1/L1...
Page 24
Firing modes 3. Chapter 3 FIRING MODES Contents Page 3.1. General and firing mode signalling ......3-2 3.2.
Page 25
Firing modes 3. Chapter 3 FIRING MODES 3.1. GENERAL AND FIRING MODE SIGNALLING 7200A power thyristor units can be controlled with one of the following thyristor firing types: • a series of supply voltage cycles with zero crossing firing (‘Burst mode’, codes C16, C64, FC1) The firing type is shown on the unit’s front panel (table 3-1) in accordance with the product code.
Page 26
Firing modes Thyristor firing in ‘Burst mode’ can be described by the firing time (T ) , non-firing time (T ) and modulation time (T ) ; where T The power delivered to the load is defined by the duty ratio η = T Firing in ‘Burst mode’...
Alarms ALARM DIAGNOSTIC The table below summarises all status LED information needed to diagnose the fault. OPTIONS Basic Version T° LEDs (Front panel) T° ≥ 125 A Orange green HEAT Green DIAGNOSIS: No Alarm Over- Partial Total heating Load Thyristor Load Firing : Failure...
Danger be inspected regularly . Given the value of the equipment controlled by the 7200A, this is strongly recommended. Eurotherm can supply various types of suitable alarm detector. 4.2. ALARM STRATEGY 4.2.1. TYPES OF ALARM Two types of alarm are available as options : •...
Alarms 4.3. ALARMS Red LED : 'Overheating' (≥125 A) Red LED : 'Serious faults' T ° Orange LED : DLF alarm G R F 'Partial Load Failure' adjustment and diagnostic push button C H K D L F S E T Figure 4-2 Layout of front panel LEDs 4.3.1.
Alarms 4.3.1.1. Alarm actions with DLF option The detection of a fault (PLF or serious alarm) is signalled by : • the corresponding LED on the front pannel of the unit • the alrm relay contact Note : DLF alarms are not memorised. LED states Firing Typical...
Alarms 4.3.2.2. Partial load failure detection PLF monitoring involves comparing the load impedance with a reference impedance stored during setting (the load impedance is calculated from the rms values measured con- tinuously). This comparison allows the detection of the load impedance increase. PLF detection is only possible under the following conditions: •...
Alarms 4.3.2.5. Signalling of channel for load fault With the ‘DLF’ option the DLF LED flashes in particular ways to indicate the controlled channel on which load failure has occurred. Figure 4-3 shows the three types of flashing if a load failure is detected on one of the channels of the 7200A power thyristor unit.
Alarms 4.3.2.5.2. Functions of DLF alarm push button The push button on the front panel of the unit with the ‘DLF’ option is labelled ‘CHK / SET’ (Checking / Setting). Pushing this push button as shown on the diagrams below sets and diagnoses the status of the PLF detection circuit.
Page 37
Important! • Eurotherm shall not be held responsible for any damage, injury, losses or expenses caused by inappropriate use of the product or failure to comply with this manual. • Accordingly the user is responsible for checking, before commissioning the unit, that all the nominal characteristics correspond to the conditions under which it is to be installed and used.
Page 38
Maintenance 5.3. THYRISTOR PROTECTION FUSES The thyristors in the 7200A power thyristor unit are protected against excess currents by high-speed fuses (for all load types other than short wave infrared elements). For current ratings ≤ 100 A the fuses are external. Danger! High-speed fuses do not provide protection for the installation.
Page 39
Maintenance USER NOTES : 7200A User Manual...
Page 40
Maintenance INDEX Page Page Alarms 1-6, Chapt. 4 Alarm relay contacts Maintenance Chapt 5 Mounting 2-3, 2-4 Bulkhead mounting Power connection Protection CE labelling Power Coding Commissioning Control connections Control signal Control teminal block Standards Safety Safety during maintenance Safety during installation Dimensions Technical Specification Three-phase load connection...
Page 41
• Data Acquisition and Management Instrumentation • Supervisory Systems (SCADA) • Process Automation Systems Eurotherm Limited is part of the of Invensys plc, one of the world’s leading automation and controls companies. Eurotherm manufactures at a number of locations in Europe and the USA, and is a major supplier to the world’s processing and manufacturing industries.