High-Voltage Connections; Connecting Ground Lead; Routing Control Power; Accessory Electric - Carrier 50ZH Series Installation, Start-Up And Service Instructions Manual

3-phase packaged heat pump
Hide thumbs Also See for 50ZH Series:
Table of Contents

Advertisement

C00007
Fig. 7--Area
Not to Be DriJJed More Than 3/4-in.
CPVC, or 3/4-in.
copper
pipe (all field supplied).
Do not undersize
tile tube. Pitch the drain tube downward
at a slope of at least 1 in.
lk)r every
I0 ft of horizontal
run. Be sure to check
tile drain
tube
liar leaks.
Prime
trap
at the
beginning
of the
cooling
season
start-up.
Allowable
glues
lot
condensate
trap
connection
are:
Standard
ABS, CPVC,
or PVC
cement.
Step
7--1nstMI
Electrical
Connections
The
unit
cabinet
nmst
have
an
nninterrupted,
unbroken
electrical
ground
to
minimize
the
possibility
of personal
injury
if an electrical
fault should
occur.
This ground
may
consist
of an electrical
wire connected
to the unit ground
in
the control
compartnlent,
or conduit
approved
lot electrical
ground
when
installed
in accordance
with
NEC
(National
Electrical
Code),
ANSI
(American
National
Standards
lnstitute)/NFPA
(latest
edition)
(in Canada,
Canadian
Elec-
trical Code CSA C22.1 ) and local electrical
codes. Failure
to
adhere to this warning
could
result in serious
injury or death.
Failure to lk_llow these precautions could result in damage to
the unit being installed:
1. Make all electrical connections in accordance with NEC
ANSI/NFPA
(latest edition)
and local electrical
codes
governing
such wiring. In Canada, all electrical connec-
tions nmst be in accordance with CSA standard C22.1
Canadian
Electrical
Code Part 1 and applicable
local
codes. Relier to unit wiring diagram.
2. Use only copper
conductor
lbr connections
between
field-supplied
electrical
disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating
voltage range indicated on unit rating plate.
4. Insulate low-voltage wires fol7 highest voltage contained
within conduit when low-voltage control wires are run in
same conduit as high-voltage
wires.
5. Do not damage internal components when drilling through
any panel to mount electrical hardware, conduiL etc. On all
3-phase units, ensure phases are balanced within 2 percent.
Consult local power company %r correction of improper
voltage and/or phase imbalance.
HIGH-VOLTAGE
CONNECTIONS
The unit nmst have a separate electrical
service with a field-
supplied, waterproof disconnect switch mounted at, or within sight
fl'om tile unit. Reler
to the unit rating plate lk)r maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) lot
wire sizing. See Table 3 lot electrical data.
The field-supplied disconnect may be monnted on the unit over the
high-voltage
inlet hole. See Fig. 2-4.
|
Operalion of nnit on inlproper lilac voltage constilnles abuse |
and may cause unit danlage lhal could allecl warranly.
J
ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect
and unit. Tile high-
voltage leads should be in a conduit until they enter the unit;
conduit termination
at the unit must be watertight.
Run the
high-voltage leads through tile hole on the control box side of the
unit (see Fig. 11 lbr location). When the leads are inside the uniL
run leads to the control box (Fig. 121. On 3-phase units, connect
the leads to the black, yellow, and blue wires (see Fig. 13).
CONNECTING
GROUND LEAD TO UNIT GROUND
Relier to Fig. 12 and 13. Connect the ground lead to the chassis
using tile nnit ground lug in tile control box.
ROUTING CONTROL POWER WIRES
Form a drip-loop with the thermostat leads belk_re routing them
into the unit. Route the thertnostat leads through grommeted hole
provided
in 1.nait into unit control box (See Fig. 11). Connect
therntostat leads and unit power leads as shown in Fig. 13 & 14.
Route thermostat wires through grommet providing a drip-loop at
the paneh Connect low-voltage leads to the thermostat as shown in
Fig. 14.
The unit translomler
supplies 24-v power %r complete
system
including accessory electrical heater. Trans%rnler is factory wired
%r 2311-voperation. If supply voltage is 208 v, rewire translimner
primary as described in the Special Procedures %r 2118-v Opera-
]ion section below.
ACCESSORY
ELECTRIC HEAT WIRING
Relier to accessory electric heat installation instructions lot inlk_r-
marion on installing accessory electric heat. Accessory electric
heat wiring is shown in Fig. 15 - 17.
SPECIAL PROCEDURES
FOR 2118-V OPERATION
Make sure that the power supply to the unit is switched OFF
and install lockout tag belk_re making any wiring changes.
Electrical shock can cause serious injury or death.
1. Remove wire nut from connection of ORG wire to BLK wire.
Disconnect the ORG translormer-primary
lead from the BLK
wire. Save wire nut. See unit wiring label.
2. Remove tile wire nut from tile temdnal on tile end of the RED
translbrnlel'-prinlal T lead.
3. Save tile wire nut.
4. Connect the RED lead to the BLK wire l?'om which the ORG
lead was disconnected. Insulate with wire nut fi'onl Step 1.
5. Using the wire nut renloved l?'onl the RED lead, insulate the
loose tertninal on the ORG lead.
6. Wrap the wire nuts with electrical
tape so that the metal
temdnals cannot be seen.
Indoor blower-motor
speeds may need to be changed %r 2118-v
operation.
Reler
to Indoor Airflow
and Airflow
Adjustments
section. (See Table of Contents lor page number.)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50zh03050zh03650zh04250zh04850zh060

Table of Contents