Cooling And Heating - Carrier 50ZH Series Installation, Start-Up And Service Instructions Manual

3-phase packaged heat pump
Hide thumbs Also See for 50ZH Series:
Table of Contents

Advertisement

SYMPTOM
Compressor
and outdoor
fan wiJl not start.
Compressor
will
not
start
but
outdoor
fan
runs.
Compressor
cycles
(other than normaJJy satisfying thermostat).
Compressor
operates
continuousJy.
Excessive
head pressure.
Head pressure too low.
Excessive
suction pressure.
Suction
pressure
too low.
Compressor
runs but
outdoor fan does not.
TabJe 8--TroubJeshooting--CooJing
and Heating
CAUSE
Power Failure
Loss of Charge
Switch open
Fuse blown or circuit breaker tripped
Defective thermostat,
contractor,
transformer,
or
control relay
Insufficient
line voltage
Incorrect or faulty wiring
Thermostat
setting too high
Faulty wiring or loose connections
in compressor
circuit
Compressor
motor burned out, seized, or internal
overload open
Defective run/start capacitor
overload
start relay
One leg of 3-phase
power dead
Low input voltage
(20 percent low)
Refrigerant
overcharge
or undercharge
Loss of Charge
Switch open
Defective compressor
Insufficient
line voltage
Blocked outdoor coil (cooling)
Defective run/start capacitor,
overload or start
relay
Defective thermostat
Faulty outdoor-fan
motor or capacitor
Restriction
in refrigerant
system
Dirty air filter
Unit undersized
for load
Thermostat
set too low
Low refrigerant
charge
Leaking valves in compressor
Frosted outdoor
coil with incorrect
defrost operation
(heating)
Air in refrigerant
system
outdoor coil dirty or restricted
Dirty air filter
Dirty outdoor coil
Refrigerant
overcharged
Air in refrigerant
system
Outdoor
or indoor air restricted
or air is recirculating
Low refrigerant
charge
Compressor
valves leaking
Restriction
in liquid tube
High heat load
Compressor
valves leaking
Refrigerant
overcharged
Dirty air filter (cooling)
Low refrigerant
charge
Metering
device or low side restricted
Insufficient
indoor airflow (cooling)
Temperature
too low in conditioned
area (cooling)
Outdoor
ambient below 40_'F (cooling)
Field-installed
filter-drier
restricted
Normally closed contacts on
defrost board open
REMEDY
Call power company
Evaluate unit for possible refrigerant
leak
Replace fuse or reset circuit breaker
Replace component
Determine
cause and correct
Check wiring diagram
and rewire correctly
Lower thermostat
setting below room tempera-
ture
Check wiring and repair or replace
Determine
cause
Replace compressor
Determine
cause and replace
Replace fuse or reset circuit breaker
Determine
cause
Determine
cause and correct
Recover refrigerant,
evacuate
system, and re-
charge to capacities
shown on nameplate
Evaluate unit for possible refrigerant
leak
Replace and determine
cause
Determine
cause and correct
Determine
cause and correct
Determine
cause and replace
Replace thermostat
Replace
Locate restriction and remove
Replace filter
Decrease
load or increase unit size
Reset thermostat
Locate leak repair, and recharge
Replace compressor
Check defrost time settings.
Reset as necessary.
Check defrost temperature
switch. Replace as necessary.
Recover refrigerant
evacuate
system
and re-
charge
Clean coil or remove restriction
Replace filter
Clean coil
Recover excess refrigerant
Recover refrigerant
evacuate
system
and re-
charge
Determine
cause and correct
Check for leaks, repair and recharge
Replace compressor
Remove restriction
Check for source and eliminate
Replace compressor
Recover excess refrigerant
Replace Filter
Check for leaks
repair, and recharge
Remove source of restriction
Increase air quantity
Check filter- replace if necessary
Reset thermostat
Install low-ambient
kit
Replace
Check condition of relay on board.
Replace board if necessary.
22