Flanges - Carrier 50ZH Series Installation, Start-Up And Service Instructions Manual

3-phase packaged heat pump
Hide thumbs Also See for 50ZH Series:
Table of Contents

Advertisement

1. Five pieces of flange are shipped on tile return-air opening of
the unit. Remove the flanges from the shipping position (See
Fig. 5). Screws are field-supplied.
2. One piece of llange is used as it is shipped (straight). Bend the
other 4 pieces at right angles.
3. Install the straight flange on tile right side of tile return-air
opening in holes provided. (See Fig. 6). Flanges should stick
out li"om unit to allow l_)r connection of ductwork.
4. Install 2 hand-lbrmed flanges onto mtum air opening in holes
provided to lbrm a rectangle around the remm air opening.
5. Install remaining 2 hand-lbmled
flanges around discharge air
opening in holes provided.
6. Duetwork can now be attached to flanges.
When designing and installing ductwork, consider the lollowing:
When connecting
ductwork
to units, do not drill deeper
than
3/4 inch
in shaded
area shown
in Fig.
7 or coil
may
be
damaged.
All units should have field-supplied
filters installed
in the
return-air side of the unit. Recommended
sizes lbr filters are
shown in Table 1.
Avoid abrupt duct size increases and reductions. Abrupt change
in duct size adversely al'li:cts air perlbmmnce.
IMPORTANT:
Use flexible connectors
between ductwork and
unit to prevent transmission
of vibration. Use suitable gaskets to
ensure
weathertight
and airtight
seal. When electric
heat is
installed, use lire proof canvas (or similar heat resistant material)
connector
between ductwork
and unit discharge connection.
If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must ectend 24 in.
li"om the unit discharge connection flange into the ductwork.
Size ductwork lbr cooling air quantity (cfln). The minimum air
quantity lbr proper electric heater operation is listed in Table 2.
Heater lindt switches may trip at air quantities below those
recommended.
Insulate and weatherproof all external ductwork. Insulate and
cover with a vapor barrier
all ductwork
passing through
conditioned spaces. Follow latest Sheet Metal and Air Condi-
tioning Contractors National Association (SMACNA)
and Air
Conditioning
Contractors
Association
(ACCA) mininmm in-
stallation standards lbr residential heating and air conditioning
systems.
Secure all ducts to building structure. Flash, weatherproof, and
vibration-isolate
duct openings in wall or ronf according to
good construction practices.
Fig. 8 shows a typical duct system with 5(tZH unit installed.
CONVERTING
HORIZONTAL
DISCHARGE
UNITS
TO
DOWNFLOW
(VERTICAL)
DISCHARGE
t
=
Belbre
perlorming
service or maintenance
operations
on
system, turn off main power to unit and install lockout tag.
Turn off accessory heater power switch if applicable. Elec-
trical shock can cause serious injury or death.
Units are dedicated side supply products. They are not convertible
to verlical air supply. A field-supplied
plenum nmst be used to
convert to vertical air discharge.
Step 6--Provide
for Condensate
Disposal
NOTE:
Be sure that condensate-water
disposal methods comply
with local codes, restrictions, and practices.
FIVE PIECES OF DUCT
FLANGE ATTACHED
HERE FOR SHIPMENT
COOOO5
Fig. 5--Shipping
Location of Duct Flanges
(Size 060 Only)
HAND FORM
STRAIGHT
PIECE
C00006
Fig. 6--Flanges
Installed
on 50ZH060 Units
Unit removes condensate
through a 1 3/64-in. 1D hole (using
314-in. OD piping or tubing) which is located at the end of the unit.
See Fig. 2-4 lbr location of condensate connection.
Condensate water can be drained directly onto the roof in rool_op
installations (where permitted) or onto a gravel apron in ground-
level installations. Install a field-supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that
the outlet of the trap is at least 1 in. lower than the drain-pan
condensate connection to prevent the pan li"om overflowing. Prime
the trap with water. When using a gravel apron, make sure it slopes
away from the unit.
If the installation
requires draining the condensate
water away
from the unit, install a 2-in. trap using a 314-in. OD robing or pipe.
(See Fig. 9 and lit.) Make sure that the outlet of the trap is at least
1 in. lower than the unit drain-pan
condensate
connection
to
prevent the pan li"om overflowing.
Prime the trap with water.
Connect a drain tube using a minimum of 314-in. PVC, 314-in.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50zh03050zh03650zh04250zh04850zh060

Table of Contents