CV Unit Zone Sensor Option
Figure I-PR-18 BAYSENS010
Dual setpoint, manual/automatic
changeover sensor with system function
lights, Accessory Model Number Digit 6 = F
CV and VAV Unit Zone
Sensor Options
Figure I-PR-19. BAYSENS014
Zone temperature sensor w/timed override
and local setpoint adjustment,
Accessory Model Number Digit 6 = C
Figure I-PR-20. BAYSENS013
Zone temperature sensor w/timed override ,
Accessory Model Number Digit 6 = B
52
Installation
BAYSENS010 Description
This zone sensor module is for use with cooling/heating constant volume units without
night setback. It has four system switch settings (heat, cool, auto, and off), two fan
settings (on and auto), and four LED's. The zone sensor provides either manual or
automatic changeover control with dual setpoint capability. In addition, it can be used
with BAYSENS017 .
BAYSENS010 features and system control functions include:
• System control switch to select heating mode (HEAT), cooling mode (COOL),
automatic selection of heating or cooling as required (AUTO), or to turn the system
off (OFF).
• Fan control switch to select automatic fan operation while actively heating or cooling
(AUTO), or continuous fan operation (ON).
• Dual Temperature setpoint levers for setting desired temperature. The blue lever
controls cooling, and the red lever controls heating.
• Thermometer to indicate temperature in the zone. This indicator is factory calibrated.
• Function status indicator lights:
• SYSTEM ON glows continuously during normal operation, or blinks if
system is in test mode.
• COOL glows continuously during cooling cycles, or blinks to indicate a
cooling system failure.
• HEAT glows continuously during heating cycles, or blinks to indicate a
heating system failure.
• SERVICE blinks or glows to indicate a problem. These signals vary
depending on the particular equipment being used.
Integrated Comfort
Applications
These zone sensor options are for use with cooling/heating Integrated Comfort System
TM
(ICS
) systems.
BAYSENS014 Description
This electronic analog sensor features single setpoint capability and timed override
with override cancellation.
BAYSENS014 features and system control functions include:
• Remote temperature sensing in the zone
• A timed override button to move an ICS
"unoccupied" to "occupied" mode.
• Thumbwheel for local setpoint adjustment
• A cancel button to cancel the "unoccupied override" command.
BAYSENS013 Description
This electronic analog sensor features single setpoint capability and timed override
with override cancellation. It is used with a Trane Integrated Comfort
BAYSENS013 features and system control functions include:
• Remote temperature sensing in the zone
• A timed override button to move an ICS
"unoccupied" to "occupied" mode.
• Cancel button to cancel the "unoccupied override" mode.
Pre-Startup
Requirements
Systems Sensors for CV and VAV
TM
or a building management system from its
or a building management system from its
TM
system.