Selection Procedures
RLA = Rated Load Amps
Compressor LRA = Locked Rotor Amps
Fan Motor LRA = Locked Rotor Amps,
N.E.C. Table 430 - 150
FLA = Full Load Amps, N.E.C.
Table 430 - 150
Voltage utilization range is ±10 percent
Determination of minimum circuit
ampacity (MCA).
MCA = 1.25 x largest motor amps/VFD
amps (FLA or RLA) + the sum of the
remaining motor amps.
Determination of maximum fuse size
(MFS) and maximum circuit breaker size
(MCB).
MFS and MCB = 2.25 x largest motor
amps (FLA or RLA) + the sum of the
remaining motor amps.
If the rating value determined does not
equal a standard current rating of over
current protective device, use the next
lower standard rating for the marked
maximum rating.
For units with the dual power option,
there are two circuits that need calcula-
tions using the formulas above:
circuit #1 - fans
circuit #2 - compressors
If the rating value determined does not
equal a standard current rating of over
current protective device, use the next
lower standard rating for the marked
maximum rating.
38
Installation
Table I-ER-1. Number of Compressors per Unit
SCWG/SIWG 20
25
SCRG/SIRG
20
10 HP
2
2
15 HP
-
-
Table I-ER-2. SCWG/SIWG Compressor Motor Data
200V
HP
RLA
LRA
10
33.1
269
15
46.9
409
Table I-ER-3. SCRG/SIRG Compressor Motor Data
200V
HP
RLA
LRA
10
38.4
269
15
55.0
409
Table I-ER-4. Fan without VFD
200V
HP
FLA
LRA
5
16.1
105
7.5
25.0
152
10
32.9
193
15
44.8
290
20
61.0
373
25
74.0
469
Table I-ER-5. Fan with VFD
200V
HP
FLA
7.5
29.0
10
38.3
15
42.7
20
55.2
25
67.8
Table I-ER-6. Electric Heat - Single Stage
SCWG/SIWG
SCRG/SIRG
Size
Size
20
20
25
25
30
-
-
32
35
-
Note:
Electric heat amperage should not be considered when determining minimum circuit ampacity. The current of the
unit in the heating mode will not exceed the current of the unit in the cooling mode.
Electrical
Requirements
30
35
25
32
1
-
1
2
460V
575V
RLA
LRA
RLA
14.4
117
11.5
20.4
178
16.4
460V
575V
RLA
LRA
RLA
16.7
117
13.4
24.1
178
19.1
460V
575V
FLA
LRA
FLA
6.7
46
5.4
10.8
66
8.2
14.2
84
11.4
20.3
126
16.2
25.0
162
20.0
31.0
204
24.2
460V
LRA
FLA
LRA
152
14.3
66
193
18.2
84
290
25.3
126
373
32.0
162
469
32.7
204
Heat
200V
Kw
Amps
16
44.8
20
55.6
24
66.8
26
72.4
28
78
LRA
94
143
LRA
94
143
LRA
37
54
66
102
132
162
460V
Amps
19.6
24.2
29.0
31.6
34.0
SCXG-SVX01B-EN