4.3.7.3.

Summary Alarm

The summary alarm is a DC potential-free contact relay.
Observe that the cross-sectional area of the wires to be connected must be in the
range from 0.14 - 1.5 mm
The following table indicates the three-connector pin out.
Pin No.
1
2
3
Page 46
2
.

figure 4-22 Summary alarm relay

Contact
Open in alarm condition
Common
Closed in alarm condition
table 4-2 Pin assignment of relay contacts
Pin 3

figure 4-23 Relay contacts, alarm condition

User's Manual for Node G
Maximum Resistive Load
Max 1 A @ 50 VDC
Max 2 A @ 30 VDC
Max 1 A @ 230 VAC