4 Functional Description
4.3.7.2.

External Alarms

The external alarms are used to monitor the status of one or more external devices
via the Node G. A UPS or entry alarm is among the items that might be connected to
the contact relay and monitored via the Node G. The cage clamp connectors are
located on the EAC-card.
Observe that the cross-sectional area of the wires to be connected must be in the
range from 0.5 - 1.0 mm

figure 4-21 Configuration of external alarm clamps

All external alarms are defaulted to high (5 VDC) without connection. This setting
may be changed on the external alarm page to active high or active low. The severity
levels of the external alarms may be set via the web page. More information about
the external alarm settings is available in the web page and online-help.
Make sure that external alarms which are not required are set to active low or disable
them; otherwise the status will always show an alarm.
The names for each external alarm are user-definable on the external alarm page;
renaming them to indicate the use of these alarms is recommendable.
Input voltage range
Recommended input line
Nominal sink current to ground
Active level
Connectors
ID No: 7164491
2
. Do not use wire-end sleeves (wire cable ends).
There are two external cage glands at the bottom of the
Main Unit, which may be used to connect the external
devices. Please note that connecting the external
devices by a wrong type of cable may result in a loss of
the water-proofness.
5 VDC
Potential free
15 mA
High or low set via software
Cage clamps
Page 45