RE112 GE-Compatible Smoke & Heat Alarm
Features
UL217 Self-Contained Fire Alarm Device
•
Senses and alarms to Smoke per UL217
•
Heat alarm at 144 degrees.
•
Sleek design.
•
Cover tamper.
•
Strong, reliable RF signal.
•
3-5 year battery life on Panasonic CR123A battery.
•
Low Battery indication.
•
Key Instructions
1. Attach the mounting plate
Locate on ceiling, as close to center as possible, away from corners.
Some local codes may allow wall mounting.
Mounting plate removes counter-clockwise
2. Insert battery with MINUS towards the RED lever. Close battery door.
3. Enroll sensor in panel:
a) Place panel in Learn Sensor mode
b) Press & release the black tamper switch
Sounder will continue beeping 3 times, until sensor is mounted.
c) Recommended GE Group # (26)
4. Testing:
a) Place panel in Sensor Test mode
b) Press & hold TEST button until you hear the sounder beep.
d) Panel will indicate the sensor is open, but Fire Alarm will not sound.
NOTE: Using Smoke-in-a-Can will cause an actual Fire Alarm.
Operation
Situation
Sounder
LED
Actual smoke
Temporal 3
RED
(Loud)
(pulsing)
Press & hold
Temporal 3
RED
Test Button
(Loud)
(pulsing)
Removing
Temporal 3
Yellow
Sensor from
(Loud)
(steady)
Mount
Low Battery
1 Chirp every
Yellow
43 seconds
(pulsing)
Hourly Check
Maintenance
Temporal 3
Yellow
Needed
(Loud)
(Pulsing)
RE112_GE-Compat_Smoke_Instructions
Page 1 of 3
24-Hour Tech Support Line: (715)808-0164
www.ResolutionProducts.com
Available for...
GE
Honeywell
2GIG
DSC
Wireless Signal
Recovery
to Panel
Wireless Fire
When smoke is no
Alarm Signal sent
longer present.
to panel
TEST button will
silence sensor for 10
minutes.
Sensor Open
Sensor: Release
signal to panel
button.
Panel: Restore when
TEST button is
released
Tamper/Trouble
Restore by
signal to be sent
remounting.
to panel.
Low battery
Supervisories,
every hour
Supervisories Not
Replace Unit
Sent
29-Oct-14
Specifications
Approval:
UL217 Self-Contained Fire Alarm Device
Smoke Sensitivity:
1.31 – 2.28 %/ft (UL 217)
0.11 – 0.165 dB/m (EN54-7)
Smoke Sensing Technology:
521)
Alarm Sound:
Temporal Three
Replacement Battery:
Panasonic CR123A
Temperature Range:
32 to 120 F (Long Term)
Humidity:
10 – 85% Relative Humidity
Housing dimensions:
4.7 inch diameter, 2.1 inch high
Design & Manufacture:
Resolution Products, Inc.
Specifications subject to change without notice.
Pictures
Tamper
Smoke Sensing
Element
Heat Sensor
TEST Button
LED
RE112_GE-Compat_Smoke_Instructions
24-Hour Tech Support Line: (715)808-0164
www.ResolutionProducts.com
Photoelectric
Mounting
Page 2 of 3
29-Oct-14
Tabs
Battery
+
Need help?
Do you have a question about the RE112 and is the answer not in the manual?
Questions and answers