Figure 5 M-2001 And M-2299 Typical Connections - BECKWITH ELECTRIC M-2001 Series Application Manual

Adapts m-2001 series digital tapchanger control to replace toshiba tb-r800 regulators
Table of Contents

Advertisement

M-2001
TAPCHANGER
CONTROL
FUNCTIONS
MANUAL RAISE
MANUAL LOWER
OFF
OP
COUNTER
NEUTRAL
NC
See Note
NO
+12 V dc
NOTE: The self-test alarm and user-programmable alarm contacts are shown in the de-energized state (no
voltage applied). The self-test alarm contacts open after the M-2001 passes the self-test; the user-program-
mable alarm contacts close when an alarm is recognized.
8 WARNING: In no case should the line current circuit be interrupted with the regulator or transformer
energized.
Do not remove auxiliary current transformers without shorting the current inputs. Death or severe
electrical shock can occur.
M-2299
ADAPTER PANEL
FUNCTIONS
OFF (MOM)
MANUAL
INT
OFF
EXT
AUTO
TO
CONTROL INT
OFF
EXT
METER OUT
VOLTAGE IN
TEST
TERMINAL
FUSE 3A
FRONT PANEL INPUTS

Figure 5 M-2001 and M-2299 Typical Connections

TB1
TB1
1
6
VOLTAGE REDUCTION STEP #2 CONTACT
2
8
3
4
7
2
5
6
3
VOLTAGE REDUCTION
STEP #1 CONTACT
7
1
8
MOTOR POWER
FUSE (6 A)
9
11
MOTOR POWER
VOLTAGE IN
FUSE (1/4 A)
10
10
NEUTRAL
NEUTRAL LIGHT SWITCH
LIGHT
5
11
N/U
12
13
4
12
14
LINE
CURRENT
15
1
SHORTING SWITCH
TB2
16
LOCAL/REMOTE
17
18
AUTO DISABLE
19
20
MANUAL RAISE
21
MANUAL LOWER
N/U
22
23
SELF-TEST ALARM (RETURN)
24
SELF-TEST ALARM (POLARITY)
25
USER-PROGRAMMABLE ALARM (RETURN)
26
USER-PROGRAMMABLE ALARM (POLARITY)
+12 V dc WETTING SUPPLY
27
–7–
M-2299 Application Guide
POLARITY CONTACT
RESISTOR NETWORK WIPER
POSITION RESISTOR
MOTOR
L
R
NEUTRAL
9
20, 21 or 22
VOLTAGE IN
on T.C.
(REGULATED
120 V)
OPERATIONS COUNTER
SWITCH
CT
CT
Toshiba Terminals
M-2299 Terminals

Advertisement