Object Data Points and Diagnostic Data Points
Table 11. All Object Types Sorted by Object Name (
Object Identifier
Object Name
Analog Input, 102
RTDM Minor Version
Analog Input, 99
RTEM Major Version
Analog Input, 100
RTEM Minor Version
Analog Input, 93
RTOM Major Version
Analog Input, 94
RTOM Minor Version
Analog Input, 91
RTRM Major Version
Analog Input, 92
RTRM Minor Version
Analog Input, 103
RTVM Major Version
Analog Input, 104
RTVM Minor Version
Binary Output, 17
Service Test Command
Binary Input, 11
Service Test Mode Status
Multi-State Input, 45
Service Test Status
Analog Input, 32
Space CO
Analog Output, 18
Space CO
Analog Output, 21
Space Dehumidification Setpoint BAS
Analog Input, 16
Space Humidity Active
Analog Output, 25
Space Humidity BAS
Analog Input, 31
Space Static Air Pressure Active
Analog Output, 10
Space Static Pressure BAS
Analog Input, 107
Space Static Pressure Setpoint Active
Analog Output, 9
Space Static Pressure Setpoint BAS
Analog Input, 15
Space Temperature Active
Analog Output, 11
Space Temperature BAS
Analog Input, 74
Space Temperature Cooling Setpoint Input
Analog Input, 75
Space Temperature Heating Setpoint Input
Analog Input, 87
Space Temperature Local
Analog Input, 50
Space Temperature Setpoint Active
Analog Output, 2
Space Temperature Setpoint BAS
Analog Input, 78
Space Temperature Setpoint Local
Analog Output, 30
Standby Offset
Binary Output, 18
Supply Air Tempering Enable Command
Binary Input, 292
Supply Air Tempering Status
Binary Output, 8
Supply Fan Configuration Command
Binary Input, 15
Supply Fan Configuration Status
Multi-State Input, 37
Supply Fan Proving Status
Analog Input, 7
Supply Fan Speed Command
Multi-State Input, 41
Supply Fan Status
Analog Input, 89
Supply Fan Type
Binary Output, 1
System Control Command
Binary Input, 1
System Control Status
Multi-State Input, 24
Timed Override Status
Analog Input, 88
Unit Energy Demand
Multi-State Input, 21
Unit Stop Source
Analog Output, 31
Unoccupied Cooling Setpoint
Analog Output, 32
Unoccupied Heating Setpoint
Binary Input, 9
VAV Box Command
34
Refer to previous tables for detailed descriptions of objects
Concentration Active
2
Concentration BAS
2
Description
Minor software version number of the RTDM module
Major software version number of the RTEM module
Minor software version number of the RTEM module
Major software version number of the RTOM module
Minor software version number of the RTOM module
Major software version number of the RTRM module
Minor software version number of the RTRM module
Major software version number of the RTVM module
Minor software version number of the RTVM module
Command the unit to step through service test
Indicates if the unit is in service test mode.
Indicates the current Service Test state
Space CO
concentration being used for unit control.
2
BAS supplied space CO
sensor value.
2
BAS supplied space dehumidification setpoint value.
The space humidity value from a unit-mounted control.
BAS supplied space humidity sensor value.
Space static air pressure value being used for unit control.
BAS supplied space static air pressure sensor value.
Space pressure setpoint currently used for unit control
BAS supplied space static air pressure setpoint value.
The space temperature currently used for unit control.
BAS supplied space air temperature sensor value.
Cooling temperature setpoint from space sensor module.
Heating temperature setpoint from space sensor module.
The space air temperature measured by a unit-mounted sensor.
Space temperature setpoint value being used for unit control.
Base value to calculate setpoints in occupied and standby modes.
The local space temperature setpoint.
Offset value used to calculate setpoints in standby mode.
Command the unit supply air tempering operation.
Indicates the status of the supply air tempering function.
Command the unit supply fan to cycling or continuous operation.
Indicates the supply fan configuration.
Indicates the current state of the supply fan.
Indicates the unit commanded supply fan speed.
Indicates the state of the supply fan.
Describes the supply fan type installed in the unit.
Command the unit to standalone- or BAS-controlled operation.
Indicates the control system currently in command of the unit.
Timed override request or cancel from zone sensor.
Indicates the current heat/cool energy demand of the unit.
Source of the stop command that turned off the equipment.
Cooling temperature setpoint used for control in unoccupied mode.
Heating temperature setpoint used for control in unoccupied mode.
Indicates whether VAV boxes should be in control or wide open.
) (continued)