What To Do After Adding Options or Equipment to the Unit

Restoring the BCI-R controller to factory defaults is necessary if the unit setup has changed after
the initial self-configuration process. This process is called "clearing the controller" .
For example, an economizer is added to the machine after the initial installation. In order for the
BCI-R controller to recognize the economizer, it must be restored to factory defaults.
The BCI-R controller self-configures upon initial power-up to match the connected equipment type.
This configuration is then permanently stored in the memory of the controller. Through this
process, the controller generates the correct list of BACnet points.

Clearing the Contoller and Restoring Factory Defaults to the BCI-R

Clearing the controller is necessary to collect equipment information and reinstall the
configuration.
Using the BACnet Setup Tool to clear the controller and restore to factory
defaults
1. Navigate to the Controller Settings screen.
2. Click within the light gray area at the bottom left of the screen just above the "Connected"
3. Click Clear Controller.
4. Click OK.
5. Click OK and then expand the Controller Units box on the Controller Settings screen.
6. Select the units (SI, IP , or Custom).
7. Click Save.
Using Tracer TU to clear the controller and restore to factory defaults
1. Establish the connection between Tracer TU and the BCI-R controller.
2. Select the Controller Settings Utility tab from the vertical tab set located on the right side of the
3. On the controller settings page, there is a gray bar at the bottom with the Save/Cancel buttons.
4. Click the Clear Controller button and a pop-up window will appear with a message that asks for
5. A pop-up window will appear confirming that the controller has been reset and that the
6. Follow the steps in

Updating the Application Code

The application code in the BCI-R controller can be upgraded in the field by using Tracer TU. Follow
the instructions in Tracer TU to upgrade the application code.
BAS-SVP09B-EN
indicator.
The Clear Controller button appears at the top right of the screen.
A message box appears stating that the configuration will be reset (deleted).
When the controller is cleared, the Select Device Units message box appears.
Defaults to Custom after clearing the controller. If you want to use Custom, ensure that all unit
options are set correctly.
TU window.
Move the cursor near the left edge of the gray bar, keeping the cursor inside the bar; click on
this area. A Clear Controller button will appear in the upper right portion of the screen display.
confirmation to reset the device. Click Yes.
controller will be restarted. Click OK. The BCI-R controller is restored to its factory default state
after it restarts.
"Using Tracer TU, " p. 7
Configuring the BCI-R
to reconfigure the BCI-R controller.