Object Types
Table 2.
Descriptions and configurations
Object
Type
Required Properties Read
Analog
• Object_Identifier
Input
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Units
Analog
• Object_Identifier
Output
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Units
• Priority_Array
• Relinquish_Default
Analog
• Object_Identifier
Value
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Units
Binary
• Object_Identifier
Input
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Polarity
BAS-SVP09B-EN
BACnet Data Points and Configuration Property Definitions
(a)
Properties Written
• Object_Name
• Description
• Out_Of_Service
• Present_Value
• Reliability
• Min_Pres_Value
• Max_Pres_Value
• Time_Delay
• Notification_Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
• Notify_Type
• Object_Name
• Description
• Out_Of_Service
• Present_Value
• Reliability
• Min_Pres_Value
• Max_Pres_Value
• Relinquish_Default
• Time_Delay
• Notification_Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
• Notify_Type
• Object_Name
• Description
• Out_Of_Service
• Present_Value
• Reliability
• Relinquish_Default
• Time_Delay
• Notification_Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
• Notify_Type
• Object_Name
• Description
• Out_Of_Service
• Inactive_Text
• Active_Text
• Present_Value
• Reliability
• Change_Of_State_Count
• Elapsed_Active_Time
• Time_Delay
• Notification_Class
• Alarm_Value
• Event_Enable
• Polarity
• Notify_Type
Optional Properties Read
• Description
• Reliability
• Min_Pres_Value
• Max_Pres_Value
• Time_Delay
• Notification _Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• Description
• Reliability
• Min_Pres-Value
• Max_Pres_Value
• Time_Delay
• Notification _Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• Description
• Reliability
• Priority_Array
• Relinquish_Default
• Time_Delay
• Notification_Class
• High_Limit
• Low_Limit
• Deadband
• Limit_Enable
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• Description
• Inactive_Text
• Active_Text
• Change_Of_State_Time
• Change_Of_State_Count
• Time_Of_State_Count_Reset
• Elapsed_Active_Time
• Time_Of_Active_Time_Reset
• Time_Delay
• Notification_Class
• Alarm_Value
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• Reliability
Ability
to
Ability to
Create
Delete
Yes
Yes, only
user created
objects
Yes
Yes, only
user created
objects
Yes
Yes, only
user created
objects
Yes
Yes, only
user created
objects
19