Operating State 83.212.Xx01.2 - Wieland podis?MOT FA C 3I/1I4O Operating Instructions Manual

Decentral field distributor at as interface
Table of Contents

Advertisement

Operation | 8
Operating state
Color Designation
83..xx0.
green AS-i power
red AS-i fault
yellow IN 0
yellow IN 1
yellow IN 2
yellow M ok
yellow OUT 0
yellow M Run
yellow OUT 2
yellow OUT 3
8.
Status
Meaning
constantly on
AS-i voltage supply is correct
off
AS-i supply is missing
constantly on
Communication error at AS interface, slave does not
participate in normal data traffic (e.g. slave address
"0")
flashing
Periphery error, e.g. short circuit of AS-i voltage
off
AS-i communication is correct
constantly on
Signal voltage IN0 high level
off
Signal voltage IN0 low level
constantly on
Signal voltage IN1 high level
off
Signal voltage IN1 low level
constantly on
Signal voltage IN21 high level
off
Signal voltage IN2 low level
constantly on
Drive operational
off
Drive not operational, no supply connected
constantly on
Signal voltage OUT0 high level
off
Signal voltage OUT0 low level
constantly on
Signal voltage OUT1 high level
off
Signal voltage OUT1 low level
constantly on
Signal voltage OUT2 high level
off
Signal voltage OUT2 low level
constantly on
Signal voltage OUT3 high level
off
Signal voltage OUT3 low level
Wieland Electric | BA000341 | 02.2007