Daikin LX10F11B3 Service Manual page 36

Inverter container refrigeration unit, decos va
Table of Contents

Advertisement

https://daikin-p.ru
1. Dehumidification set
Dehumidification Set
OFF
▲▼:Change
ENTER:Confirm
※2-3 Bulb Mode Set
1. Press
or
key to select "ON" or "OFF" and press
ON : Bulb mode operation is conducted. (For unit equipped with humidity sensor)
OFF : Bulb mode operation is not conducted.
2. After selecting "ON", press
key to determine.
3. Press
or
key to select the defrost completion temperature in the range of 4.0℃ to 18.0℃ and
press
key to determine.
※ If it is necessary to set the humidity, do so according to the procedure in 2-2 Dehumidification Set.
1. Bulb mode selection
Bulb mode
OFF
▲▼:Change
ENTER:Confirm
※2-4 USDA Set
1. Press
key to select number of sensors and press
4 sensors :4 USDA sensors connected
3 sensors :3 USDA sensors connected
AUTO
:Automatically recognize the number
 of USDA sensors connected (Note 1)
OFF
:No USDA sensor connected
Dehumidification Set
ON
▲▼:Change
ENTER:Confirm
or
key to select "L", "H-L", or "H" for the EFM speed and press
Bulb mode
ON
▲▼:Change
ENTER:Confirm
USDA
OFF
▲▼ : Change
ENTER : Confirm
2. Humidity setpoint selection
Humidity Setpoint
95 % RH
▲▼:Change
ENTER:Confirm
Humidity Setpoint
75 % RH
▲▼:Change
ENTER:Confirm
key to determine.
2. EFM speed setting
Bulb mode
Evap Fan Speed
L
Def
Temp
18.0℃
End
 ▲▼:Change
Confirm
ENTER:
key to determine.
Note 1: To measure the temperature inside or cargo
temperature for the purposes other than cold
treatment transport, USDA sensor can record the
temperature ranging from –30.0 ℃ to +40 ℃ .
Do not use it for cold transport treatment
because it does not meet the USDA standards.
USDA
4 sensors
▲▼ : Change
ENTER : Confirm
2-7
Mode Set screen
3. Defrost completion temperature
Bulb mode
Evap Fan Speed
L
Def
Temp
15.0℃
End
 ▲▼:Change
Confirm
ENTER:
Mode Set screen