INSTRUCTIONS FOR INSTALLATION AND USE.
CDC122T1R2
CDC122T1R3B
CDC122T1R3G
CDC122T1R3J
We thank you for choosing an LAE controller. Before proceeding to the installation of the CDC 12, please read this instructions sheet carefully;
only in this way you will obtain maximum performances and safety.

1. INSTALLATION

1.1 The CDC122T1R2 and CDC122T1R3B have got a size of 77x35x77 mm (WxHxD), while the CDC122T1R3G and CDC122T1R3J have got a
size of 77x35x97 mm (WxHxD). The instrument is inserted into the panel through a 71x29 mm hole and secured via the suitable brackets exerting
corret strength. The rubber gasket must be placed between the panel and the instrument front, so please make sure that there are no gaps allowing
liquid infiltrations.
1.2 The unit works with an ambient temperature between -10°...+50°C and 15%...80% relative Humidity. To reduce the effects of electro-magnetic
interference, place the cables carrying signals (probes and serial connections etc.) and the controller as away as possible from power lines.
1.3 Probes, power supply, inputs and outputs must be wired strictly following the diagram indicated on the enclosure, where the maximum loads also
appear. For supply voltage, the suitable transformer (mod. TRxxx) must be used.
1.4 Probe T1 measures air temperature and is used for the thermostat function; probe T2 measures the evaporator temperature and must be secured
to it on the place where the maximum frost growth occurs.
1.5 The remote defrost start input needs an external activation voltage between 10 ... 16Vac, 10mA. When this voltage is applied to the input,
defrost is started.
1.6 The RS485 serial communication port or, if fitted, the TTL ouput for the remote display is available on the DATA connector. PIN 1 is identified by
a dot.
Caution:
• If the relays switch a large load frequently, we suggest you contact us to obtain information about the relay contact life.
• Where delicate or valuable products have to be maintained under strict conditions, please use a different controller for limit and alarm functions.

2. CONTROL PARAMETERS

The adaptation of the CDC 12 to the system that it controls is achieved through the parameters in the SETUP. Access to the parameters is obtained
by pressing
+ +
for 4 seconds. Scroll through the parameters by pressing
of
and change it via
+
to the following table.
or
. Exit from the SETUP occurs after 10 seconds of no key activation. To help yourself during programming, refer
SPL minimum programmable temperature
SPh maximum programmable temperature
hyS thermostat on switching hysteresis
coF cooler minimum off time
con cooler minimum on time
cdc cooler safety run in case of probe failure
crS cooler re-start delay after power failure
drE hours between two defrosts
dLi
dto defrost time-out
drP drain time
diS display control during defrost
dty defrost type
doP time count for defrost optimisation
Fct
FrS fan re-start after defrost
Fid
Alo low alarm threshold
Ahi high alarm threshold
AdL temperature alarm delay
Ain alarm temperature selection
oS1 thermostat probe offset
oS2 evaporator probe offset
oS3 displayed probe offset
SiM slowdown of displayed temperature
Adr peripheral number
or
until you select the desired one. Check its value by means
defrost limit temperature
evaporator fan control
[-01=always on; 00=on/off with cooler; 1... 10 minutes=delayed off]
ventilation during defrost
[+01 ... +20°K]
[00 ... 10 minutes]
[00 ... 10 minutes]
[00=off ... 10(0)%=always on]
[00 ... 120 seconds]
[01 ... 99 hours]
[01 ... 120 minutes]
[00 ... 10 minutes]
[-01="dEF"; 00="T3"; 1... 30 minutes=timed "dEF"]
[FAn=off cycle; ELE=electrical; GAS=hot gas]
[con=continuous; Acc=frost accumulation]
[00=off; 01=T2<FrS; 02=always on]
[-01=excluded; 00... 120 minutes]
[temperature 1, 2, 3]
[-50 ... +150°]
[SPL ... +150°]
[+01 ... +70°]
[-50 ... +150°]
[-50 ... +150°]
[ALo ... +150°]
[-20 ... +20°K]
[-20 ... +20°K]
[-20 ... +20°K]
[00 ... 200]
[00 ... 255]

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CDC122T1R2 and is the answer not in the manual?

Questions and answers

Summary of Contents for LAE electronic CDC122T1R2

  • Page 1 1. INSTALLATION 1.1 The CDC122T1R2 and CDC122T1R3B have got a size of 77x35x77 mm (WxHxD), while the CDC122T1R3G and CDC122T1R3J have got a size of 77x35x97 mm (WxHxD). The instrument is inserted into the panel through a 71x29 mm hole and secured via the suitable brackets exerting corret strength.
  • Page 2 INSTRUCTIONS FOR INSTALLATION AND USE. 3. DISPLAYS 3.1 D . At the power up, the display shows "---" for 5 seconds during which the unit carries out a self-check; then the URING ORDINARY ONTROL temperature T3 appears. In some cases, owing to the structure of the cabinet or air stratification, the probes can not measure the desired temperature. If necessary, through the parameters oS1, oS2 and oS3 the temperatures t1,and t2 measured by the probes can be adjusted in order to obtain the desired values for computing: thermostat T1=t1+oS1;...
  • Page 3 WARRANTY LAE electronic Srl warrant that their products are free of any defects in workmanship and materials for a period of 1 (one) year from date of production shown on the enclosure. LAE electronic Srl shall only repair or replace those products of which defects are due to LAE electronic Srl and recognised by their technicians.
  • Page 4 INSTRUCTIONS FOR INSTALLATION AND USE. SETUP -50 ... 150 SPL ... 150 01 ... 20 00 ... 10 00 ... 10 00 ... 10 00 ... 120 01 …. 99 01 ... 70 01 ... 120 00 ... 10 -01 ... 30 FAn;...

This manual is also suitable for:

Cdc122t1r3bCdc122t1r3jCdc122t1r3g

Table of Contents

Save PDF