STULZ the natural choice Technical Manual STULZ UltraSonic Humidifier System for direct room humidification BNB BNB 1000A BNB 4000A BNB 2000A BNB 5000A BNB 3000A BNB 8000A Original user guide - Read carefully before use - Version 10-2015 - Keep for later reference -...
Page 2
STULZUltraSonic-SystemforDirectRoomHumidificationBNB- Dear Customer, Many thanks for choosing to buy a STULZ product. STULZ has been a purveyor of sophisticated technical solutions for comfort and precision air conditioning applications since 1947. Best regards, STULZ GmbH Hotline For general inquiries, please get in touch via our hotline on +49 40 5585 252 or hotline@stulz.de/en.
Any other use besides or beyond this shall be regarded as improper use. STULZ cannot be held liable for damages resulting from the above. The risk shall be borne by the plant operator alone.
Before restarting, the preparatory measures in the Installa- tion/Start-up section must be carried out. • T heunitsmayonlybeconvertedormodifiedfollowingconsultationwithSTULZGmbH.Genuine spare parts and parts/accessories approved by STULZ GmbH are a guarantee of safety. • Never operate the system without the necessary protective covers. •...
We recommend the use of genuine spare parts. Genuine spare parts and spare parts/accessories ap- proved by STULZ GmbH are a guarantee of safety. The spare parts list can be found in the following section:"13. Spare parts lists" on page 91. To order spare parts, call the hotline or your specialist retailer.
BNB 1000 A BNB 4000 A BNB 2000 A BNB 5000 A BNB 2000 A BNB 5000 A STULZ UltraSonic BNB Quick-start Guide BNB 3000 A BNB 8000 A BNB 3000 A BNB 8000 A M25121 VERSION 06.2015 | 1000647 | DE Version 06-2015 Art.Nr.
STULZUltraSonic-SystemforDirectRoomHumidifi cationBNB- Product description The STULZ UltraSonic BNB model series is designed fordirectroomhumidifi cationusing ultrasonic atomization. Here, an transducer installed in a water bath produces a cold mist, which is expelled out of the unit into the room by an integrated fan.
4.4. Operating principle of ultrasonic humidifi cation Ultrasonichumidifi ersfromtheSTULZUltraSonicmodelseriesworkontheprincipleof ultrasonic atom- ization.A48Valternatingvoltageisrectifi edonan nebulizer print plate and converted into a high-fre- quency signal of 1.65 MHz. This signal is transferred to an transducer installed in the water bath, which converts it into a high-frequency mechanical oscillation.
Thewaterpressuretotheultrasonichumidifiermustbebetween0.5barand6bar,thewatertemperature between 8°C and 40°C. ** See drawing "4.6. Dimensional drawing" on page 19 *** When connected to a STULZ USM control cabinet and using factory settings. For installing in an on-site switch gear cabinet Uptohumidifiercapacityof3l/h Selecting the required open-loop/closed-loop control system...
If this ultrasonic system is used in an application with nooronlyaminimalsupplyofoutsideair(e.g.equipmentrooms),itmayhappenthatminerals/salts enter the room via the air humidifying system and are deposited on surfaces. To prevent this, we urgent- lyrecommendtheinstallationofdownstreamdemineralizingequipmentwithconductivitymonitor(e.g. STULZ ion exchanger SD 2800 incombinationwiththeSTULZconductivitymeasuringkit). ® CAUTION NOTICE Demineralized drinking water.
Page 25
Systeme so sicher wie möglich konstruiert und betrieben werden. Stellungnahme Bei den Ultrasonic-Befeuchtern der Firma Stulz kann das hygienische Risiko als niedrig angesehen werden. Es ist Dr. Holger Brill (Arbeitshygieniker) davon auszugehen, dass die hochfrequenten Schwingungen im Ultraschall-Befeuchter Bakterien in ihrer Lebend- keimzahl reduzieren.
STULZUltraSonic-SystemforDirectRoomHumidificationBNB- Design and planning Thissectiondealsonlybrieflywiththemainaspectsofdesignandplanning.Youcanobtainmore detailed information in our STULZ UltraSonic Planning Guide. Please refer to our STULZ UltraSonic Planning Guide for more information. Visit our e-stulz page on the internet at www.stulz.de/en/e-stulz. Hereyoucandownloadourcertificates. Foreffectiveplanning,youmusttakeaccountofdifferentsizesandboundaryconditions: 1) Installation conditions Location(elevationabovesealevel)
RC element. NOTICE CAUTION The wrong contactor coils can cause damage. Different contactor coils can damage the unit! Use genuine STULZ spare parts. ● Accessory set for controlling the STULZ UltraSonic humidifier Interference Proportional Item Con tac- Transformer Condenser element...
Switch gear cabinets must be wired as shown in the wiring diagrams provided. ● CAUTION Genuine parts. Use only genuine STULZ parts and genuine spare parts for installation. NOTICE CAUTION Horizontal position. The unit must be mounted precisely horizontally.
Select the right type of installation to suit local circumstances. The examples below show the installation ofaBNBultrasonichumidifieronabracketandinatray.Iftheultrasonichumidifierismountedonawall bracket,thesafetyoverflowmustbeconnectedtothedrainviaahose.Ifitisnotpossibletoconnectthe safetyoverflowtothedrain,theultrasonichumidifiercanbeinstalledinatrayinwhichawatersensor isfitted.Installtheunitsuchthatthemistexpelledbythefanisdistributeduniformlyeverywhereinthe room.(Alsoseesection"5. Design and planning" on page 26).Persons in the blow-out area of the humidifiermustmaintainadistanceofapprox.5.0m.Boththewallbracketandsafetytrayareavailable fromSTULZasoptionalaccessories(seesection"3.1. Optional accessories" on page 13). CAUTION Installation in an elevated location. Ifinstallingthehumidifierinanelevatedlocation,makesurethatitiseasilyaccessibleforadjustments, inspections,maintenanceandrepairwork.Insufficientspacecancausemaintenancepersonnelto suffer injuries and accidents! CAUTION Bear local conditions in mind.
Page 48
Installation STULZUltraSonic-SystemforDirectRoomHumidifi cationBNB- 7.4.2.3. Drain connection for safety tray The safety tray is available from STULZ as an optional accessory (seesection"3.1. Optional accessories" on page 13). Ø 25 Proceedasfollowstoconnectthedrainforthesafetytray: Clean all components. Ø 25 Pushthedrainagehose(insidediameter 25mm)overthesafetytrayfi tting.
The main menu is a display menu in which you can read the operating parameters during operation. It varies depending on which operating mode is selected. ● Start-up menu: Thestart-upmenuisaparameterizationmenu,inwhichyoucancarryoutthefollowingsettings: Stulz Ultrasonic Master/Slave Steuergeräte (USM/USS) Start-up menu mode Operatingmode(factorysetting=1) capacit Capacity,limitationofhumidifiercapacity(factorysetting=1=100%)
Page 64
Operation STULZUltraSonic-SystemforDirectRoomHumidificationBNB- drü Proceed as follows to change to the main menu: und zusä Menüaufbau Anwe Stulz Ultrasonic Master/Slave Steuergeräte (USM/USS) ca. 5 s C Press "OK". betätigen Befeuchtungssteuerung ü Befeuchter mode Ext. Anford. capacit 1.00 Anfrd supp 15.00...
Page 65
Default setting 4 Input2:Roomsensor(0-1V) humidity is limited to an adjustable maximum Monitoring for sensor fracture value. *For alternative options, see TH STULZ UltraSonic master/slave control units USM/USS. **Factory setting Note CAUTION Parameterization. The parameter that is to be set depends on the type of signal from the humidity sensor. Please read the technical documentation of the humidity sensor.
Page 66
Menüaufbau Anwe Operation STULZUltraSonic-SystemforDirectRoomHumidificationBNB- Stulz Ultrasonic Master/Slave Steuergeräte (USM/USS) Befeuchtungssteuerung ü drü Proceed as follows to set the operating mode: und zusä ca. 5 s C Mainmenu(factorysetting)isselected. betätigen Menüaufbau Anwe Befeuchter Humidifier Stulz Ultrasonic Master/Slave Steuergeräte (USM/USS) Ext. Anford.
Page 67
Ext. Anford. capacit 1.00 Anfrd supp 15.00 Ausg: room 20.00 drü drü und zusä Grundmenü Stulz Ultrasonic Master/Slave Steuergeräte (USM/USS) ca. 5 s C The main menu opens betätigen (application5). Befeuchter room Ext. Anford. setpoint Anfrd supp Ausg: Befeuchter-Me outpt drü...
Page 68
Stulz Ultrasonic Master/Slave Steuergeräte (USM/USS) drü Befeuchtungssteuerung ü Operation STULZUltraSonic-SystemforDirectRoomHumidificationBNB- und zusä ca. 5 s C Press and hold the "Esc" button until the betätigen -> setpoint cursor is under the first parameter. Befeuchter room 00055 Ext. Anford.
This would damage the unit, as it has no water in this position. ● CAUTION Genuine spare parts. Only genuine STULZ spare parts may be used. CAUTION Risk of injury from sharp edges. • Make sure that all persons and specialist engineers wear the appropriate protective equipment (gloves,helmet,safetygoggles)fortheirwork...
STULZUltraSonic-SystemforDirectRoomHumidificationBNB- Start-up Checklist Start-up Checklist for STULZ UltraSonic® Humidifiers The technical documentation of all units to be started up and their accessories is to hand All humidifiers are precisely horizontal and securely mounted Clearances and distances have been complied with...
Comments: Watercontactloop(ENS14+18) Damaged Comments: STULZ GmbH Klimatechnik Company headquarters is Hamburg Directors:J.Stulz(Chairman), Holsteiner Chaussee 283 Hamburg District Court HRB 16255 Dr. U. Görge, M. Stulz, 22457 Hamburg, Germany VAT ID No. DE 811 207 224 M. Zimmermann...
Page 107
Final check of entire system Comments Date Signature STULZ GmbH Klimatechnik Company headquarters is Hamburg Directors:J.Stulz(Chairman), Holsteiner Chaussee 283 Hamburg District Court HRB 16255 Dr. U. Görge, M. Stulz, 22457 Hamburg, Germany VAT ID No. DE 811 207 224 M. Zimmermann...
Page 108
Exclusion of liability TheSTULZGmbHcompanyreservestherighttoadapttheproductspecificationsorcircuitdiagramsinlinewithtechnical d evelopments,modificationstotheequipmentorfuturemarketrequirements. All previous versions of this manual become void upon the publication of this one. Hamburg, June 2015...