MAN0814-01
3

GENERAL OPERATION

AC/DC Input
Power
100-240 VAC /
140-340 VDC
ON Switch /
Short Circuit
Jumper Block
Figure 3 – General Operation
1.
For output and short circuit protection, ensure that the Switch/Short Circuit jumper block is
installed and properly seated.
2.
Adjust the current (using Potentiometer A) for maximum load current protection by rotating fully
clockwise.
3.
Connect the power (100-240 VAC / 140-340 VDC).
4.
Adjust the output voltage (using Potentiometer V) to 24 VDC.
5.
Connect the load to the output terminal.
4
Remote Control Switching (RPS) Function
The RPS function allows the control of the output voltage using a remote control switch.
AC/DC Input
Power
100-240 VAC /
140-340 VDC
External Switch
(K1)
Figure 4 –RPS Function
1.
Remove the Switch/Short Circuit jumper block. Wire an external switch (K1).
2.
Adjust the current (using Potentiometer A) for maximum load current protection by rotating fully
clockwise.
No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, Inc.
Information in this document is subject to change without notice.
02 AUG 2006
+24 VDC
Ground
Current Adjust
Voltage Adjust
(Pot. A)
(Pot. V)
+24 VDC
Load
Ground
Storage
Battery
Voltage
Current
Adjust
Adjust
(Pot. V)
(Pot. A)
Warning:
Storage
Battery
PAGE 3
Be sure to wire the load
observing the proper
polarity on the unit and
ensure that the
maximum working
current is ≤ 3 A.