Blocking
Error
code
164
LOWEXFLOW_
PROTECTION
165
VSUPPLY_TOO
_LOW
166
VSUPPLY_TOO
_HIGH
Table 5.3

Warnings

Warning
Warning
no.
200
CC_LOSS_
COMMUNICATION
202
APP_SELECTION_
ERROR
203
CC_LOSS_BOILER_
COMM
204
OUTDOOR_WRONG
205
T_SYSTEM_WRONG
206
T_CASCADE_WRONG
Table 5.4
27
Description
Flow is too low, demand
needs to be stopped with
fan at ignition speed*, but
no error needed to be
stored at this time
Main supply voltage too low
for more than 60 seconds
Main supply voltage too
high for more than 60 sec.
Description
Cascade System:
Managing cascade control
lost communication with
one of the depending.
Unknown appliance model
selected
Dual Cascade System:
Managing cascade control
lost communication with
one of the depending.
T_Outdoor sensor
measures open/shorted
T_System sensor
measures open/shorted
T_Cascade sensor
measures open/shorted
E95.1901EN032 User manual Slant Fin VGH-CH / CO
Cause
Solving
not enough water
If the boiler does not start
flow through heat
after Reset, contact your
exchanger
installer
dip in power supply
Check power supply
to boiler
peak
in
power
Check power supply
supply to boiler
Cause
connection between
cascaded boilers is
interrupted or wiring
is broken
wrongly
programmed
parameters
connection between
cascaded boilers is
interrupted or wiring
is broken
malfunctioning
outdoor sensor or
not connected or
wrong CH-mode
programmed
malfunctioning
system sensor or
not connected
malfunctioning
cascade sensor or
not connected
Solving
Contact your
installer
Contact your
installer
Contact your
installer
Contact your
installer
Contact your
installer
Contact your
installer