FUNCTION

20
FUNCTION

Forced Cooling Operation

Adding the refrigerant in winter.
Setting Procedure
- Set the Dip Switch as follow after shutting the power source down.
ATUQ24GPLE6
APUQ24GS1A3
APUQ30GR5A3
* Some model don't have this function.
- Reset the power.
- Red LED and Green LED of PCB lights during work. (The indoor unit is operated by force.)
- If operation is done, Red LED will be turned off.
If operation is not done normally, Red LED will blink.
- Close the Liquid valve only after green LED turned off (7 minutes from the start of the machine).
Then close the gas valve after Green LED on.
!
WARNING
• When the green LED of PCB is on, com-
pressor is going to be off because of low
pressure.
• You should return the Dip Switch to oper-
ate normally after finishing the operation.
• Improper Pump down will lead to product
turn off along with LED (green &red) off
with in 20 minutes from the initial start.
ATUQ30LNLE6
ATUQ36GNLE6
ATUQ36LNLE6
APUQ36GR5A3
APUQ36LR5A3
ATUQ48GMLE6
ATUQ48LMLE6
APUQ48GT3E3
APUQ48LT3E3
Pump Down Dip S/W Setting
Power on
(Red LED On, Green LED Off)
Comp on
(Red LED On, Green LED On)
Pump Down Start
(Red LED On, Green LED Off)
Pump Down Complete
(Red LED Off, Green LED On)
Power off
(Red LED Off, Green LED On)
Liquid Valve
Closed
Gas Valve
Closed