® Multi Axes System Installation Manual Edition: D, February 2020 Valid for MKD-C-NA, Hardware Revision B Valid for MKD-N, Hardware Revision B Part Number 904-200003-00 Original Document For safe and proper use, follow these instructions. Keep for future use.
Page 2
Technical changes which improve the performance of the device may be made without prior notice! This document is the intellectual property of Kollmorgen. All rights reserved. No part of this work may be reproduced in any form (by photocopying, microfilm or any other method) or stored, processed, copied or distributed by electronic means without the written permission of Kollmorgen.
6.2.1 MKD-C modules 6.2.2 MKD-N modules 6.3 Part Number Scheme 6.3.1 MKD-C modules 6.3.2 MKD-N modules 7 Technical description and data 7.1 The MKD Multi Axes System 7.2 Mechanical Data 7.3 Performance Data 7.4 Electrical Data Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 4
9.5.2 Topology example with two external strings 9.5.3 Topology example with one external string migrated to cabinet 9.6 Connection Overview 9.6.1 Connector Position MKD-C 9.6.2 Connector Position MKD-N (6A, 12A) 9.6.3 Connector Position MKD-N (24A) Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 5
9.11.1.2 Motor Power X29, Motor Brake X30, Motor Feedback X31 9.11.2 Motor dual cable connection (X29, X30, X32) 9.11.2.1 Motor Power and Motor Brake X29 9.11.2.2 Motor Power X29, Motor Brake X30 9.11.2.3 Motor Feedback X32 9.12 Secondary Feedback Connection (X33) Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 6
10.1.13 Local STO on AKD-N 10.1.13.1 General information 10.2 Brake interruption contact 10.2.1 General information 10.2.2 Safety instructions 10.2.3 Signal diagram (sequence) 10.2.4 Enclosure, wiring 10.2.5 Technical data and connection 11 Setup 11.1 Important Notes Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 7
Et h e r C AT c a b l e s 1 4 3 1 4 3 1 4 3 1 4 4 1 4 4 12.4 Spare Parts 13 Index 14 Record of Document Revisions Kollmorgen | kdn.kollmorgen.com | February 2020...
MKD Installation Manual | 2 General 2 General 2.1 About this Manual 2.2 Using the PDF Format 2.3 Symbols Used 2.4 Abbreviations Used Kollmorgen | kdn.kollmorgen.com | February 2020...
Table of contents and Lines are active cross references. Click on the line and the appro- index priate page is accessed. Page/chapter numbers Page/chapter numbers with cross references are active links. in the text Kollmorgen | kdn.kollmorgen.com | February 2020...
Incremental encoder (A quad B) Specific thermal resistance Safe Brake Control Safe Brake Test Super Capacitor SELV Safety Extra Low Voltage Safe torque off To be discussed (in process) Volts, alternating current Volts, direct current Kollmorgen | kdn.kollmorgen.com | February 2020...
MKD Installation Manual | 3 Product Safety 3 Product Safety 3.1 You should pay attention to this 3.2 Shock-hazard Protection 3.3 Stop / Emergency Stop / Emergency Off 3.4 Use as Directed 3.5 Prohibited Use 3.6 Warning note labels Kollmorgen | kdn.kollmorgen.com | February 2020...
(Warning: Automatic Restart at Power On) and ensure, that power on is not pos- sible, while humans are in a dangerous zone of the machine. In case of using an under- voltage protection device, you must observe EN 60204-1:2006 chapter 7.5 . Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 15
EN13849 or EN 62061 must finally be done by the user. Never modify the drive! It is not allowed to modify the drive hardware without permission by the manufacturer. Open- ing the housing causes loss of warranty. Kollmorgen | kdn.kollmorgen.com | February 2020...
(schematic connection (➜ # 80). A ground-leakage mon- itor can be used to monitor for short circuits. Keep the length of wiring between the transformer and the drive as short as possible. Kollmorgen | kdn.kollmorgen.com | February 2020...
If necessary, provision must be made for the connection of protective devices and lock-outs. If applicable, the stop function must signal its status to the control logic. A reset of the stop function must not create a hazardous situation. Kollmorgen | kdn.kollmorgen.com | February 2020...
This results in a category 0 stop. If this stop category is not possible in the applic- ation, then the Emergency Off function must be replaced by other measures (for example by protection against direct touching). Kollmorgen | kdn.kollmorgen.com | February 2020...
/√2). nMotor For the cases of group installations and of DC powered drives MKD-C has not been evaluated by Kollmorgen, UL, or TÜV for group installations nor are rat- ings defined for DC input voltage. Auxiliary voltage supply, Standby power Standby power for the drive strings must only be used for supplying the MKD-N electronics.
Wiring the system with hybrid cables from other manufacturers than Kollmorgen is not allowed. Changing Kollmorgen cables or connectors is not allowed. 3.6 Warning note labels If these signs are damaged, they must be replaced immediately.
Less than 1 year: without restriction. More than 1 year: capacitors in the MKD-C must be re-formed before setting up and operating the system. Re-forming procedures are described in the Kollmorgen Developer Network (Forming). Kollmorgen | kdn.kollmorgen.com | February 2020...
80 °C (176 °F). Before touching the device, check the temperature and wait until it has cooled below 40 °C (104 °F). 3. Remove the connectors. Disconnect the potential earth connection last. 4. Demount: loosen the fastening screws. Remove the device. Kollmorgen | kdn.kollmorgen.com | February 2020...
In accordance with the WEEE-2012/19/EU guideline and similar, the manufacturer accepts returns of old devices and accessories for professional disposal. Transport costs are the responsibility of the sender. Contact Kollmorgen and clarify the logistics. Send the devices in the original packaging to the manufacturer address: North America...
MKD Installation Manual | 5 Approvals 5 Approvals 5.1 Conformance with UL/cUL 5.2 Conformance with REACH 5.3 Conformance with EU Low Voltage, EMC and RoHS Directives 5.4 Conformance with EU Machinery Directive, Functional Safety Kollmorgen | kdn.kollmorgen.com | February 2020...
MKD Installation Manual | 5 Approvals 5.1 Conformance with UL/cUL MKD system products covered in UL file number E217428, Power Conversion Equipment: MKD (Modular Kollmorgen Drive) Decentral System, consisting of Power supply MKD-CXXXX07-XXXX-XXXX and Inverter module MKD-NXXXX07-XXXX-XXXX and/or AKD-N3/6/12 with connection cables cat. no. MKC-HYB-x-AKN-XXX, and/or CCNNN1-025-XXXXX-00.
Kollmorgen declares the conformity of the MKD modules with the following directives: EC Directive 2014/35/EU, Low Voltage Directive Used harmonized standard EN 61800-5-1...
5.4 Conformance with EU Machinery Directive, Functional Safety Conformance with the EC Machinery Directive 2006/42/EU is mandatory for the supply of safety components within the European Community. Kollmorgen declares the conformity of the MKD modules with the following directives: EC Directive 2006/42/EU, Machinery Directive...
Cables (➜ # 143) Cabinet grommets (➜ # 86) Accessories for AKD-N see regional Accessories Manual or AKD-N Installation Manual. Spare parts Connectors and Connector Kits can be ordered as spare parts (➜ # 144). Kollmorgen | kdn.kollmorgen.com | February 2020...
The nameplates depicted below are attached to the side of the device. Pictures are similar to the nameplates on the device. 6.2.1 MKD-C modules Example for MKD-C-NA 6.2.2 MKD-N modules Example for MKD-N single axis, 6A Kollmorgen | kdn.kollmorgen.com | February 2020...
06 A 06 A MKD-N1200 12 A MKD-N1206 12 A 06 A MKD-N2400 24 A MKD-N1212 12 A 12 A MKD-N4800 48 A Customization code coding for customer specials (not relevant for functional safety). Kollmorgen | kdn.kollmorgen.com | February 2020...
STO voltage 24V DC (functional safety circuits) From an external, 24 V ±10% PELV power supply, or from safety controller. Power depends on application. Operation and parameter setting Using the setup software WorkBench for setup via TCP/IP. Kollmorgen | kdn.kollmorgen.com | February 2020...
Switching frequency of output stage Voltage rise speed dU/dt kV/µs Bandwidth of current controller Bandwidth of velocity controller (scalable) 0 to 750 0 to 600 Bandwidth of position controller (scalable) 1 to 250 Maximum motor frequency Kollmorgen | kdn.kollmorgen.com | February 2020...
Protection class IP20 * Do not exceed continuous rating of 30 kW over the profile cycle. ** Two MKD-C CA are operated in parallel via DC bus sharing with a current limit set to 20A Kollmorgen | kdn.kollmorgen.com | February 2020...
CE Region DC-Bus link fusing 50 A (Time-Delay) Eaton: Siba (FD1/2) FWP-50A14F 400V to 480V: aR 50A Supercap fusing max. 32 A Mersen: HP10M25 (25 A) or HP10M30 (30 A) or (FD1/2) HP10M32 (32 A) Kollmorgen | kdn.kollmorgen.com | February 2020...
I/O connector MKD-C 24 V supply ground MKD-C STO-GND STO 24 V ground MKD-C internal digital ground, service channel MKD-N DCOM common line for digital inputs on I/O connector MKD-N STO-GND STO 24 V ground Kollmorgen | kdn.kollmorgen.com | February 2020...
Feedback DSL/SFD3 0.3 to 0.5 2.6 to 4.4 X32A/B Feedback, Con- 0.3 to 0.5 2.6 to 4.4 ventional X33A/B Feedback , 2. Feed- 0.3 to 0.5 2.6 to 4.4 back PE Bolt Protective Earth 15.0 Kollmorgen | kdn.kollmorgen.com | February 2020...
IEC 60204. For information on the chemical, mechanical, and electrical characteristics of the cables please contact our customer support. Use Kollmorgen hybrid, motor, and feedback cables only. You will lose system warranty, if you use hybrid, motor or feedback cables from a manufacturer other than Kollmorgen.
X13, X15, X16, X24, X26 If total motor cable capacitance exceeds 2.25 nF (phase / phase) or 3.75 nF (phase / shield), then a motor choke must be used with cables longer than 25 m. Kollmorgen | kdn.kollmorgen.com | February 2020...
External regen resistor Maximum continuous regen power Regen chopper current Peak regen power, external (1s) Absorption energy in capacitors (+/- 20%) DC Bus Capacitance (nominal) µF 1500 1500 * depends on connected regen resistor power Kollmorgen | kdn.kollmorgen.com | February 2020...
RUN (Green) and Error (RED) status. EtherCAT L/A LEDs: These are the EtherCAT Link/Activity LEDs associated with the Motion Bus IN (X10) and OUT (X11) ports. Activity description seetable above. Kollmorgen | kdn.kollmorgen.com | February 2020...
ON = active, OFF = not active LED12 7.15 Push-button (B1) The push-button on the MKD-C can be used to start predefined functions. Press short to display the IP address in the LED display Kollmorgen | kdn.kollmorgen.com | February 2020...
IP address independent of the rotary switch is available. More information is available in the MKD-C User Guide or in the Settings Screen-> Fieldbus-> TCP/IP screen in WorkBench. Kollmorgen recommends to use AutoIP addressing. Set S1 to 0 (zero) for DHCP/AutoIP address. Dynamic IP addressing (DHCP and Auto-IP)
5. Ground the modules. For EMC-compliant shielding and grounding, (➜ # 60). Ground the mounting plate, the motor housing, the GND of the 24 V supply and CNC-GND of the control system. Kollmorgen | kdn.kollmorgen.com | February 2020...
Implement the wiring according to the connection diagrams: (➜ # 64). It is permissible to use the setup software to alter the settings of the device. Any other alter- ations will invalidate the warranty. Kollmorgen | kdn.kollmorgen.com | February 2020...
Check proper use of residual-current circuit breakers (RCD, (➜ # 16)) l. Connect the PC (➜ # 107) for setting up the drive system. 6. Check the wiring and observe the system topology limits (➜ # 61). Reinstall the front protection cover: Kollmorgen | kdn.kollmorgen.com | February 2020...
Single cable motor connection: Connect the hybrid motor cable to X4, max. length 5 m. 4. Check the wiring against the planned system topology (➜ # 61) and the wiring diagrams in the AKD-N Installation manual. Kollmorgen | kdn.kollmorgen.com | February 2020...
Use Kollmorgen cables. Route unshielded power and control cables separately, Koll- morgen recommends a distance of at least 200 mm to improve interference immunity.
9.4.2.3 Local fieldbus connectors X21A, X21B The shield of local fieldbus cables is connected via the connector to the housing. Kollmorgen | kdn.kollmorgen.com | February 2020...
You can control up to 3 motor brakes per string. Available power for brakes is 76 W per string (= 3.2 A @ 24 VDC). Service Interface X18 Ethernet TCP/IP, 100 Mbit/s, max. cable distance 100 m Kollmorgen | kdn.kollmorgen.com | February 2020...
MKD Installation Manual | 9 Electrical Installation 9.5.2 Topology example with two external strings Kollmorgen | kdn.kollmorgen.com | February 2020...
MKD Installation Manual | 9 Electrical Installation 9.5.3 Topology example with one external string migrated to cabinet Kollmorgen | kdn.kollmorgen.com | February 2020...
Slow, isolated, sink, type EN 61131-2 type 1 Digital-In 3 Slow, isolated, sink, type EN 61131-2 type 1 DCOM Ground for digital I/O Digital-Out+ Slow, isolated, sink, type EN 61131-2 type 1 Digital-Out- Slow, isolated, sink, type EN 61131-2 type 1 Kollmorgen | kdn.kollmorgen.com | February 2020...
MKD-C, MKD-N, front 3 slide contacts with screws Connects DC-Bus link between modules Details: (➜ # 87) Pin Signal Description + DC DC bus link + - DC DC bus link - Protective earth Kollmorgen | kdn.kollmorgen.com | February 2020...
9.6.6.14 X25: MKD-C, DC Bus sharing MKD-C, bottom 3 pin, pitch 10.16 mm With shield plate Wiring example DC-Bus: (➜ # 87) Pin Signal Description + DC DC-Bus link + - DC DC-Bus link - n.c. not connected Kollmorgen | kdn.kollmorgen.com | February 2020...
X27 IN port, X28 OUT port Node ID to be set by WorkBench Interface Details: (➜ # 84) Signal Description Transmit + Tx - Transmit - Rx + Receive + Rx - Receive - Kollmorgen | kdn.kollmorgen.com | February 2020...
9.6.6.19 X30A: MKD-N 24A or 48A, Motor Brake MKD-N, bottom 2 pin, pitch 3.81 mm required for SIL3 brake control Wiring example motor brake: (➜ # 92) Pin Signal Description Motor holding brake + Motor holding brake - Kollmorgen | kdn.kollmorgen.com | February 2020...
DAT+ Zero+ Zero+ COM- DAT- DAT- DAT- DAT- Zero- Zero- +5 V +5 V +5 V +5 V +5 V +5 V +5 V CLK = Clock, DAT = Data, Th = thermal control Kollmorgen | kdn.kollmorgen.com | February 2020...
Input for secondary feedback X33A for Axis 1, X33B for Axis 2 if applicable Wiring examples secondary Feedback: (➜ # Sine / Cos Incr. Enc. Shield Shield Zero+ Zero+ Zero- Zero- +5 V +5 V Kollmorgen | kdn.kollmorgen.com | February 2020...
This page illustrates all the possible connection variations for different electrical supply net- works. Rated supply voltage (TT network) for MKD-C is 400/480 VAC. An isolating transformer is required for non TT networks or other voltage ratings. Kollmorgen | kdn.kollmorgen.com | February 2020...
Directly to 3-phase supply network (➜ # 80), 400/480 VAC, 50/60 Hz Fusing (such as fusible cut-outs, FN1/2/3) to be provided by the user: (➜ # 38). Available Mains Chokes: (➜ # 140) Signal Description Line 1 Line 2 Line 3 Protective Earth Kollmorgen | kdn.kollmorgen.com | February 2020...
Fusing (such as fusible cut-outs, FA1) to be provided by the user: "Fusing" (➜ # 38). Signal Description +24 VDC Auxiliary voltage 24V Supply GND Kollmorgen | kdn.kollmorgen.com | February 2020...
24 VDC supply for emergency ramp down or brake situations. Cable which exit the cabinet, should be threaded through grommets. To ensure protection class IP67, Kollmorgen recommends cable entry system KDL/S com- bined with cable entry grommet KDT/S manufactured by: Murrplastik Systemtechnik GmbH Fabrikstraße 10...
X22 to X27 or X28 to X27 are connected via the short EtherCAT Module cable (➜ # 143). Signal Description Transmit + Tx - Transmit - Rx + Receive + Rx - Receive - These port may not be directly connected to standard EtherCAT or Ethernet TCP/IP nodes. Kollmorgen | kdn.kollmorgen.com | February 2020...
The DC power lines supply DC power for up to 14 AKD-N drives in one string. Connection for the DC power must be done by a mating connector with strain relief due to EMC reasons. This interface is connected via the Kollmorgen MKC-HYB-z-AKN cable. Pin Signal Description...
(➜ # 42). Use external fusing for device protection. Fusing (such as fusible cut-outs, FD1/FD2) to be provided by the user: (➜ # 38) . Signal Description DC Bus link positive DC Bus link negative n.c. not connected Kollmorgen | kdn.kollmorgen.com | February 2020...
The supercapacitor must be discharged via an external regen resistor. Example wiring for discharging (➜ # 90). The manufacturer of the machine must generate a risk assessment for the sytem with super- cap. Kollmorgen | kdn.kollmorgen.com | February 2020...
Check or set the current regulator value (max. 20A) via keyword VBUS.MAINSCURRENTLIMIT Adjust Precharge timeout or set to 0 s via keyword VBUS.PRECHARGETO Save to Device The supercapacitor must be discharged via an external regen resistor. Example wiring for discharging (➜ # 90). Kollmorgen | kdn.kollmorgen.com | February 2020...
2. Switch of power supply for the MKD-C-CA devices ('Lock' contact closes). 3. Close switch S0 (discharge) and keep it closed for the discharging time analyzed during the risk assessment. 4. Switch off mains power. Regen resistor (R1) sizing Contact Kollmorgen support for help, please. Kollmorgen | kdn.kollmorgen.com | February 2020...
The regen circuit +RB/-RB is short circuit proof. Observe the prohibition of continuous, oper- ational short circuits to the external regen resistor contacts (➜ # 20). Pin Signal Description External Regen Resistor positive External Regen Resistor negative Protective Earth Kollmorgen | kdn.kollmorgen.com | February 2020...
Only install motors with insulation class F (acc. to IEC60085) or above. Only install Kollmorgen cables that meet the requirements: (➜ # 42). Motor Brakes A 24 V holding brake in the motor can be controlled directly by the drive. The brake works with sufficient 24 V voltage level only.
MKD-N 24 A or 48 A axes Signal Description Motor phase U Motor phase V Motor phase W Protective earth (motor housing) Signal Description Motor Brake positive Motor Brake negative Signal Description COM+ SFD3/DSL positive COM- SFD3/DSL positive Kollmorgen | kdn.kollmorgen.com | February 2020...
9.11.1.1 Motor Power and Motor Brake X29, Motor Feedback X31 Valid for MKD-N axes with 6 A or 12 A. 9.11.1.2 Motor Power X29, Motor Brake X30, Motor Feedback X31 Valid for MKD-N axes with 24 A or 48 A. Kollmorgen | kdn.kollmorgen.com | February 2020...
MKD-N 24 A or 48 A axes Signal Description Motor phase U Motor phase V Motor phase W Protective earth (motor housing) Signal Description Motor Brake positive Motor Brake negative Signal Description 1...15 See (➜ # 97) Kollmorgen | kdn.kollmorgen.com | February 2020...
9.11.2.1 Motor Power and Motor Brake X29 Valid for MKD-N axes with 6 A or 12 A. 9.11.2.2 Motor Power X29, Motor Brake X30 Valid for MKD-N axes with 24 A or 48 A. Kollmorgen | kdn.kollmorgen.com | February 2020...
Zero- +5 V +5 V +5 V +5 V +5 V +5 V +5 V CLK = Clock, DAT = Data, Th = thermal control BiSS Mode C interface from Renishaw (model Resolute RA26B) Kollmorgen | kdn.kollmorgen.com | February 2020...
Input for secondary feedback X33A for Axis 1, X33B for Axis 2 if applicable X33B is available in dual-axis modules only. Sine / Cos Incr. Enc. Shield Shield Zero+ Zero+ Zero- Zero- +5 V +5 V Kollmorgen | kdn.kollmorgen.com | February 2020...
OFF: 0 VDC to 12 VDC, < 50 mA immunity 60 VDC STO outputs (X24) as per IEC61131-2 type 1 max. 30 VDC, 100 mA short circuit proof galvanic isolation for 30 VDC Update rate 62.5 µs Kollmorgen | kdn.kollmorgen.com | February 2020...
STO-Enable String 3 + STO String 3 + Global STO Enable String of 3 (➜ # 115) STO-Enable String 3 - STO String 3 - STO Ground GND STO Ground of 24 V STO supply Kollmorgen | kdn.kollmorgen.com | February 2020...
+ 24 V STO 24V STO supply voltage STO-Enable + STO + Local STO Enable + (➜ # 119) STO-Enable - STO - Local STO Enable - STO Ground GND STO Ground of 24 V STO supply Kollmorgen | kdn.kollmorgen.com | February 2020...
ENABLE signal (Terminal X15B/1). Enable is possible only if the input STO-String 2 or 3 (valid for DC power strings 2 or 3) have a 24 V signal (➜ # 109) and Software Enable is set. In the disabled state the connected motors have no torque. Kollmorgen | kdn.kollmorgen.com | February 2020...
Connector X26 on MKD-N offers access to local STO input signals of the included axes in the MKD-N module. There is one local STO-Enable input for each axis. For description of STO interface and functionality refer to (➜ # 109). Kollmorgen | kdn.kollmorgen.com | February 2020...
- Contact closed when there is no fault and the drive is enabled. Technical characteristics: Relay output, max. 30 VDC or 42 VAC, 1 A Time to close: max. 10 ms Time to open: max. 10 ms Wiring diagram: Kollmorgen | kdn.kollmorgen.com | February 2020...
Can be wired as sink or source (current sourcing in the example below) Update rate: 250 µs Wiring diagram: * On MKD-N connector X24A is used for axis 1, X24B is used for axis 2 if built-in. Kollmorgen | kdn.kollmorgen.com | February 2020...
4, 5 n.c. n.c. Receive- Transmit - 7, 8 n.c. n.c. 9.14.2 EtherCAT MKD-C can be connected as slaves to the EtherCAT network (CoE) via RJ-45 connectors X10 (in port) and X11 (out port). Kollmorgen | kdn.kollmorgen.com | February 2020...
Signal Transmit + n.c. Transmit - Receive- Receive+ n.c. n.c. n.c. 9.15.2 Service Bus Protocols Protocol Type Ethernet TCP/IP Service Bus, 100 Mbit/s Network hubs and transfer rate of 10 Mbit/s are not supported. Kollmorgen | kdn.kollmorgen.com | February 2020...
STO. Even if the STO function will be issued for a whole year, this event will only hap- pen every 100 Billion years. The STO Status signals are informal and not relevant for functional safety. Kollmorgen | kdn.kollmorgen.com | February 2020...
Emergency-Off situations. In an Emergency-Off situation, the main contactor is switched off (by the Emergency-Off button). Wiring the system with hybrid cables from other manufacturers than Kollmorgen is not allowed. Changing cables or connectors is not allowed. MKD-N have not to be used for driving elevators.
Test pulses with T1 ≤ 300 µs and T2 ≥ 200 ms will not have any influence to the safety rel- evant STO function. Test pulses, which are outside of this specification, will switch the STO function, but will not create a dangerous situation. Kollmorgen | kdn.kollmorgen.com | February 2020...
The delay from falling edge at global STO Enable input until energy supply to the motors is interrupted, depends on the number of connected MKD-N to the string. Maximum reaction time is 10 ms. The more MKD-N are connected to the string, the shorter is the reaction time. Kollmorgen | kdn.kollmorgen.com | February 2020...
Based on the standards according to EN60204-1 or EN 13849-1, you must implement a restart interlock. The design and execution depends on the respective risk assessment of the application and its safety level as well as safety rating. Kollmorgen | kdn.kollmorgen.com | February 2020...
10.1.11.1 General information (global STO) The global STO function uses the following devices: MKD-C, AKD-N without option "DS" or "DT", Kollmorgen hybrid connection string cable. There is one STO input and one STO-Status output for every DC Power string. The string STO input release the power output stage of all AKD-N (without option DS/DT) connected to the string as long as a 24 V signal is applied to this input.
STO inputs of an MKD-C device to SIL2, PLd. Both drive strings are switched independently. Kollmorgen KSM modules cannot be used. Environment notes and wiring requirements: (➜ # 110). Kollmorgen | kdn.kollmorgen.com | February 2020...
When wiring the STO circuits within a enclosure, the cables and the enclosure must meet the requirements of IEC 60204-1. If you are wiring leads outside the specified enclosure, then the cables must be laid durably and protected from outside damage. Use Kollmorgen cables only.
2. Activate the global STO function, for example, by opening protective screen (voltage at STO input = 0V). 3. The corresponding string STO-Status message changes the voltage level, the string can- not be enabled. Kollmorgen | kdn.kollmorgen.com | February 2020...
Pinout connector STO output signals X24 A Axis 1 X24 B Axis 2 1...3 Digital In 1...3 1...3 Digital In 1...3 DCOM DCOM 5...6 Digital Out 5...6 Digital Out STO-Status + STO-Status + STO-Status - STO-Status - Kollmorgen | kdn.kollmorgen.com | February 2020...
STO inputs of a dual-axis MKD-N drive module to SIL2, PLd. Both axes strings are switched independently. Kollmorgen KSM modules cannot be used. Environment notes and wiring requirements: (➜ # 110). Kollmorgen | kdn.kollmorgen.com | February 2020...
Second Method: 1. Stop the drive with setpoint 0 V, disable drive. 2. Activate the STO function, for example, by opening protective screen (voltage at input STO = 0V) 3. The drive cannot be enabled. Kollmorgen | kdn.kollmorgen.com | February 2020...
The local STO input on the AKD-N and MKD-N have no influence to the global STO as well. The local AKD-N STO functionality is described in the AKD-N installation manual. Refer to the AKD-N Installation Manual for full information. Kollmorgen | kdn.kollmorgen.com | February 2020...
Ensure that the jumper is removed (➜ # 123). Test the brake function regularly, for example with a standardized SBT. 10.2.3 Signal diagram (sequence) Fault F305 will be activated, if the sequence requirements given below are not fulfilled. Kollmorgen | kdn.kollmorgen.com | February 2020...
Ensure that the jumper is removed, if you want to connect the external safety device. Pinout connector X9 X9 A Axis 1 X9 B Axis 2 BrInt Out BrInt Out BrInt In BrInt In Wiring Example for axis 1 Environment notes and wiring requirements: (➜ # 122). Kollmorgen | kdn.kollmorgen.com | February 2020...
Use ear protection if the control cabinet has to be opened during normal operation. If the MKD-C has been stored for more than 1 year, you must re-form the capacitors in the DC bus link circuit. Re-forming procedures are described in the Kollmorgen Developer Net- work (Forming).
All connected devices must have static IP addresses. Refer to the WorkBench Online Help for more information. EtherCAT Node Address The EtherCAT node address is assigned automatically by the EtherCAT master. Refer to WorkBench Online Help and EtherCAT manual for more information. Kollmorgen | kdn.kollmorgen.com | February 2020...
The MKD-C forwards the Ethernet packets to all connected drives and returns the response packets. Every connected axis has a unique MAC address and can be viewed as standalone Ethernet device (client). Example Auto-IP system Refer to the WorkBench Online Help for more information. Kollmorgen | kdn.kollmorgen.com | February 2020...
This chapter describes the installation of the setup software WorkBench for MKD-C and MKD-N drives. Kollmorgen offers training and familiarization courses on request. 11.3.1 Use as directed The setup software is intended to be used for altering and saving the operating parameters for the MKD and AKD series of products.
Connection to the Ethernet interface of the PC Connect the interface cable to an Ethernet interface on your PC or to a Switch and to the service interface X18 of the MKD-C (➜ # 107). Kollmorgen | kdn.kollmorgen.com | February 2020...
Using WorkBench, you can now configure the drive through this connection. 11.4.3 Install and start WorkBench WorkBench is available from the DVD included with the drive and on the Kollmorgen Web- site: www.kollmorgen.com. Select the install file and follow the instructions given by the installer.
Power board EEPROM corrupted serial number data. F213 Power board EEPROM corrupted parameter stamp. F214 Power board EEPROM corrupted parameter data. F219 Control board EEPROM write failed. F230 Power board EEPROM write failed. F232 Power board EEPROM invalid data. Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 134
String 1 over current. F581 String 2 over current. F582 String 3 over current. F583 Rectifier desaturated. F584 Total string current over peak limit. F587 All AC input phases lost while drive was enabled. Kollmorgen | kdn.kollmorgen.com | February 2020...
F139 Target position overshot due to invalid motion task activation. n151 Not enough distance to move; motion exception. n152 Not enough distance to move; following motion exception. n153 Velocity limit violation, exceeding max limit. Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 136
Brake open circuit. F306 Brake short circuit. F307 Brake applied during enable state. F308 Voltage exceeds motor rating. n309 Motor I²t load. F312 Brake released when it should be applied. F401 Failed to set feedback type. Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 137
Wake & Shake - Motor V phase missing. F485 Wake & Shake - Motor W phase missing. F486 Input change rate exceeds maximum speed of emulated encoder. F487 Wake & Shake - Validating positive movement Failed. Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 138
EMUEMODE incompatible with DRV.HANDWHEELSRC. F621 Control Board CRC fault. F623 Power Board CRC fault. F624 Power Board Watchdog fault. F625 Power Board Communication fault. F626 Power Board FPGA not configured. F627 Control Board Watchdog fault. Kollmorgen | kdn.kollmorgen.com | February 2020...
Drive problems occur for a variety of reasons, depending on the conditions in your applic- ation. The causes of faults in multi-axis systems can be very complex. If you cannot resolve a fault, Kollmorgen customer support can give you further assistance. Eliminate errors and faults in compliance with work safety rules. Troubleshooting only by qualified and trained staff.
12.3.2.2 Dimensions and Data Protection class: IP20 High Temperature! The surface temperature can exceed 250°C. Risk of burns and fire! Measure the temperature before touching. Use fusing (e.g. FPS) to prevent the resistor from being overloaded. Kollmorgen | kdn.kollmorgen.com | February 2020...
Disassemble Marquages UL Disposal Mechanical Data Document Revisions MKD Multiaxes System Dynamic Braking Motor interface Motor overload protection Mounting position Electrical Data Emergency Off Emergency Stop Function Nameplate ENABLE Noise Emission Enclosure protection EtherCAT Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 146
Hardware requirements Functional Safety Installation Product Safety Operating systems Safety Instructions Brake Interruption Drive Setup Electrical Installation General Mechanical Installation Service Interface Setup Setup Software Shielding Shock-hazard protection Site Site altitude Stacking Height Storage Transport Kollmorgen | kdn.kollmorgen.com | February 2020...
Chapter used standards removed, electrical data completed, 42kA rating, DC-Bus chapter com- C, 09/2019 pleted, SuperCap notes added, Brake interruption contact completed, UL markings updated, Chapter functional safety completed D, 02/2020 Thermal dissipation and efficiency factor added Kollmorgen | kdn.kollmorgen.com | February 2020...
Page 148
About KOLLMORGEN Kollmorgen is a leading provider of motion systems and components for machine builders. Through world- class knowledge in motion, industry-leading quality and deep expertise in linking and integrating standard and custom products, Kollmorgen delivers breakthrough solutions that are unmatched in performance, reliability and ease-of-use, giving machine builders an irrefutable marketplace advantage.