4.
Configuring Power Monitor
Firstly, please change the protocol from MEWTOCOL to MODBUS in the Power Monitor and set communica-
tion parameters as follows:
• Baud Rate:
19200
• Parity:
Odd
• Data Bits:
8
• Stop Bits:
1
Start the Weidmüller Power Monitor Manager.
STEP 26
Under [Settings] select [Communication setup].
STEP 27
1502950000/01/03.15
Configuring Power Monitor
15