Toshiba V Series User Manual page 19

Integrated controller
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

• Status LED
RDY (green)
RUN (green)
TOKEN (green)
ERR (red)
ACC(green)
• Configurator port (CONFIG)
PC (PROFIBUS-DP configurator) connector.
• Transmission cable terminating resistor specification switch (TERM)
TERM (terminating resistor) → ON: Terminated with terminating resistor. Turn on at
nodes on both ends.
• Transmission cable connector (PROFIBUS-DP)
PROFIBUS-DP transmission cable connector
• Reset switch (RESET)
Press when the PF311 is abnormal or when initializing the PF311 independent of the
controller.
• Loader port (LOADER)
PC (loader for use by TOSHIBA maintenance personnel) connector.
(Normally not used.)
6F8C0921
Table 2-2 Status LED
ON
Transmission module normal
Slow flash
Firmware not stored.
(1 Hz)
Fast flash
Hardware error or system error or in downloading
(4 Hz)
firmware configuration data
OFF
Hardware failure
ON
Communicating
Cyclic flash
Standby
(4 Hz)
Acyclic flash
Configuration error or fatal error
ON
Token retained
OFF
No token
ON
Error on communication line
OFF
No error detected
ON
Controller accessing
OFF
Controller not accessing
2.4 Name of PF311 Module Components and Parts
2
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3000 profibus

Table of Contents