Bryant 619E Series Installation, Start-Up And Service Instructions Manual

High wall fan coil units, sizes 018 and 024,1 1/2 and 2 tons

Advertisement

Quick Links

IMPORTANT - READ BEFORE INSTALLING
1. Read and become familiar with these installation in-
structions before installing this unit (see Fig. 1).
2. Be sure the installation conforms to all applicable local
and national codes.
3. These instructions contain important information for the
proper maintenance and repair of this equipment. Re-
tain these instructions for future use.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
I. Complete Pre-Installation Checks . . . . . . . . . . . . . 2
II. Select Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
III. Mount Mounting Bracket on Wall . . . . . . . . . . . . . . 4
IV. Connect Refrigerant Piping . . . . . . . . . . . . . . . . . . . 5
V. Connect Condensate Drain Line . . . . . . . . . . . . . . 6
VI. Make Electrical Connections . . . . . . . . . . . . . . . . . 7
VII. Make Connections to Outdoor Unit . . . . . . . . . . . . 8
Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-12
I. 619E Control System . . . . . . . . . . . . . . . . . . . . . . . . 9
II. After Extended Shutdowns . . . . . . . . . . . . . . . . . . . 9
III. Seasonal Changeovers . . . . . . . . . . . . . . . . . . . . . . 9
IV. To Turn The Unit On and Off . . . . . . . . . . . . . . . . . 10
VI. Operating Mode Memory . . . . . . . . . . . . . . . . . . . . 10
VII. Automatic Operation (Auto) Mode . . . . . . . . . . . . 10
VIII. Operating Fault Diagnosis . . . . . . . . . . . . . . . . . . 10
IX. Microprocessor Control Operation . . . . . . . . . . . 10
CLEANING AND MAINTENANCE . . . . . . . . . . . . . . . . . 12-14
I. Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
III. To Set the Current Time . . . . . . . . . . . . . . . . . . . . 12
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
V. To Clean Indoor Unit Front Panel . . . . . . . . . . . . . 13
VI. To Clean Indoor Coil . . . . . . . . . . . . . . . . . . . . . . . 13
VII. To Clean Outdoor Coil . . . . . . . . . . . . . . . . . . . . . . 13
VIII. To Clean Condensate Drains . . . . . . . . . . . . . . . . 14
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
I. Diagnostic Codes . . . . . . . . . . . . . . . . . . . . . . . . . . 14
II. System Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
III. System Safeties and Interlocks . . . . . . . . . . . . . . 14
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-17
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . CL-1, CL-2
installation, start-up and
service instructions
HIGH WALL FAN COIL UNITS
Page
Cancels: New

SAFETY CONSIDERATIONS

Recognize safety information. This is the safety-alert symbol
(
). When you see this symbol on the unit and in instruc-
tions or manuals, be alert to the potential for personal
injury.
Understand the signal words - DANGER, WARNING, and
CAUTION. These words are used with the safety-alert sym-
bol. Danger identifies the most serious hazards which will
result in severe personal injury or death. Warning indicates
a situation that could result in personal injury. Caution is
used to identify unsafe practices which would result in minor
personal injury or product and property damage.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit. Electrical shock could cause personal injury.

GENERAL

The new 619E heat pump high wall fan coil units (Fig. 1) DO
NOT have electric heaters. These new heat pump fan coil units
have been specifically designed to improve system efficiency
in both heating and cooling modes when matched with a 538B
outdoor heat pump unit. If your application requires heat-
ing, heat pump units must be used, both outdoors and in-
doors. See Table 1 for recommended system combinations.
INSTALLATION
The 619E cooling only high wall fan coil unit is installed with
either the 538A condensing or 538S multi-split condensing
outdoor unit, and the 619E heat pump fan coil unit is in-
stalled with the 538B heat pump outdoor unit. Refer to
Table 1 to make sure the correct indoor unit(s) is installed
with the correct outdoor unit.
Installation instructions for the 619E fan coil units are con-
tained in this manual. Refer to this manual for proper instal-
lation of the complete system. Note that the 538A, 538B, and
538S outdoor units are shipped with installation and service
instructions for basic installation of the outdoor section. Be
sure to make the modifications in Make Connections to Out-
door Unit section on page 8 of this literature so that the out-
door unit will operate properly with the 619E control system.
Be sure the unit will be operated within the application guide-
lines shown in Table 2. When installing the 538A, 538B, or
Fig. 1 - 619E High Wall Fan Coil Unit
619E
Sizes 018 and 024
1
1
and 2 Tons
2
II 619E-18-1
4/15/96

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 619E Series

  • Page 1: Table Of Contents

    installation, start-up and 619E service instructions Sizes 018 and 024 ⁄ and 2 Tons HIGH WALL FAN COIL UNITS Cancels: New II 619E-18-1 4/15/96 IMPORTANT — READ BEFORE INSTALLING SAFETY CONSIDERATIONS 1. Read and become familiar with these installation in- Recognize safety information.
  • Page 2: Installation

    538S unit, note that for cooling operation below 55 F (538A, Table 2 — Application Ranges 538B) or 0°F (538S), it is necessary to equip the outdoor unit COOLING MODE with the low ambient control (538A, 538B) or winter start Maximum Minimum (538S) accessory.
  • Page 3 UNIT WEIGHT 619E 018 39 Lb [17.5 Kg] 619E 024 43 Lb [19.5 Kg] NOTES: 1. Dimensions in [ ] are in millimeters. Direction if airflow. 3. Refrigerant, drain, and power connections may be made in unit rear, bottom, left side, or right side. 4.
  • Page 4: Mount Mounting Bracket On Wall

    *A clearance of 4 is the absolute minimum. A clearance of 10 is recommended. NOTE: Remove unit front cover for control box access. *538A, 538B/538S Systems. Fig. 3 — Minimum Required Clearances Fig. 5 — Maximum Line Lengths III. MOUNT MOUNTING BRACKET ON WALL 1.
  • Page 5: Connect Refrigerant Piping

    Fig. 6 — Bracket Mounting Use the following instructions to connect piping. 1. Install insulation. Insulate all refrigerant lines on heat pumps 538S and systems to prevent condensation. It is extremely important that all refrigerant lines and the AccuRater metering device be insulated on heat pumps. On 538A cooling only units, the liquid line may be left uninsulated.
  • Page 6: Connect Condensate Drain Line

    3. Insulate and caulk wall openings to reduce air infiltra- Table 3 — Specifications tion and refrigerant pipe vibrations on structure. UNIT 619E 4. Evacuate piping, if necessary. If either refrigerant pip- OPERATING WEIGHT (lb) ing or the indoor coil is exposed to atmospheric condi- REFRIGERANT R-22 with AccuRater Control or TXV tions, it must be evacuated to 1000 microns to elimi-...
  • Page 7: Make Electrical Connections

    Fig. 12 — Drainage System (Rear Piping Shown) 5. Route factory-supplied line power leads (see Fig. 14) from VI. MAKE ELECTRICAL CONNECTIONS field-supplied, indoor unit disconnect to the fan coil unit Be sure field wiring complies with local building codes and TB1 (see Fig.
  • Page 8: Make Connections To Outdoor Unit

    Table 5 — Electrical Data INDOOR MAX FUSE OPERATING VOLTAGE* V (Single- UNIT WATTS OR HACR TYPE Ph, 60 Hz) 619E CKT BKR AMPS 018† 024† 208/230 0.53 0.66 018** 024** LEGEND *Permissible limits of the voltage range at which unit will operate satisfactorily.
  • Page 9: Start-Up

    Fig. 16 — Mounting Unit to Bracket also have thermistors located on the outdoor coil and in the START-UP outdoor air inlet. These thermistors monitor system opera- Complete the following checks and the Start-Up checklist on tion and control the operating mode. To change settings or page CL-1 before system start-up.
  • Page 10: To Turn The Unit On And Off

    IV. TO TURN THE UNIT ON AND OFF To turn the unit on, press the orange ON/OFF button (See Fig. 18). Unit will start. To stop unit operation, press the ON/ OFF button again. Unit will stop. Refer to Owner’s Manual enclosed with the fan coil unit for full remote control operat- ing details.
  • Page 11 change operating speeds depending on the room tempera- temperature. The reversing valve will be off. The compres- ture. If the room temperature is below the set point, the sor cannot run for 3 minutes from the time the system starts indoor fan will run at ultra-low speed, and the compressor up or for 3 minutes from the time it last operated.
  • Page 12: Cleaning And Maintenance

    3. Press the RST button using an instrument screw- driver or similar small, pointed tool. 4. Replace the cover securely. EMER — Emergency Mode It is time to replace the remote controller batteries when the remote controller function becomes irregular, or the system Fig.
  • Page 13: To Clean Indoor Unit Front Panel

    REMOVE COVER INSERT NEW BATTERIES PRESS RST NOTE: Be sure to insert new batteries correctly (as shown). Fig. 21 — Installing or Replacing Batteries PRESS TA SET TIME PRESS TA Fig. 22 — Setting the Current Time REMOVE FILTER VACUUM CLEAN RINSE WITH WATER Fig.
  • Page 14: To Clean Condensate Drains

    VIII. TO CLEAN CONDENSATE DRAINS A. Thermistor Tests Clean all drains and drain pans at the start of each cooling Each thermistor is tested for high limit out of range (shorted season. Check the flow by pouring water into the drain. condition) and low limit out of range (open condition).
  • Page 15: Troubleshooting

    TROUBLESHOOTING See Table 8 and Fig. 24 and 25 to assist in troubleshooting the 619E fan coil units. Table 8 — Troubleshooting PROBLEM POTENTIAL SOURCE ACTION Unit does not Circuit breaker has tripped or fuse is blown Reset the circuit breaker or replace the fuse. operate Power failure Restart fan coil unit operation when power is restored.
  • Page 16 —16—...
  • Page 17 —17—...
  • Page 18 Copyright 1996 Carrier Corporation CATALOG NO. BDP-3361-904...
  • Page 19: Start-Up Checklist

    START-UP CHECKLIST I. PRELIMINARY INFORMATION INDOOR UNIT: MODEL NO. SERIAL NO. OUTDOOR UNIT: MODEL NO. SERIAL NO. ACCESSORIES: __________________________________________________________________________________ PISTONS (538A AND 538B SYSTEMS ONLY): INDOOR SIZE: OUTDOOR SIZE (538B SYSTEMS ONLY): REFRIGERANT PIPING: EQUIVALENT LINE LENGTH: (IF OVER 50 FT)* LIFT: FAN COIL ABOVE OUTDOOR UNIT (IF OVER 25 FT)*? FAN COIL BELOW OUTDOOR UNIT (IF OVER 25 FT)*? *APPLIES ONLY TO 538A AND 538B UNITS USING LONG-LINES APPLICATIONS.
  • Page 20 START-UP CHECKLIST (cont) HAS PIPING SYSTEM BEEN EVACUATED TO 1000 MICRONS (IF REQUIRED)? HAS SYSTEM CHARGE BEEN WEIGHED IN (IF REQUIRED)? HAVE SERVICE VALVES BEEN FULLY BACKSEATED? CHECK VOLTAGE: IS VOLTAGE WITHIN RANGE SHOWN FOR UNIT (WITH UNIT OPERATING)? OUTDOOR INDOOR START-UP IF UNIT HAS A CRANKCASE HEATER, HAS IT BEEN ON FOR 24 HOURS?

Table of Contents