ABB Automation Products AB
Version: Initial version
Version: Initial version
Issue date: May 2000
Issue date: May 2000
In service
Start
Trip
Front layout
RXHL 422
Compact current relay
CONNECTION AND SETTING GUIDE
General
in
Made
The compact current relay RXHL 422 is available to order in four different
Sweden
variants, more information is available on page 4.
Location:
Pressure:
Temperature:
Humidity:
Ingress protection:
Installation category:
Electric safety class:
Frequency:
Rated current:
Rated voltage:
Auxiliary voltage:
Power consumption:
Binary-input:
Binary-output:
Indications
LED indications:
Without removing the plastic cover the primary service values,
indications and primary trip values can be checked and cleared
by pushing the "C" button.
Push button
Let you...
1. Move upwards in menu tree.
2. Turn-off display at main menu.
C
3. Read service values and disturbance information.
1. Confirm choices in menu.
E
2. Move downwards in menu tree.
1. Move left in dialog boxes and editable menus.
2. Move upwards in menu tree.
3. Turn-off display at main menu.
1. Move right in dialog boxes and editable menus.
2. Move downwards in menu tree.
1. Move upwards in specific menu.
2. Increase editable values.
3. Select choice in dialog box and configuration.
1. Move downwards in specific menu.
2. Decrease editable values.
3. Select choice in dialog box and configuration.
1MRK 509 057-WEN
Partially weather protected locations,
switchgear environment, class 3K3
80-106 kPa
-5° C to +55° C (permitted range)
-40° C to +70° C (storage range)
10-90%
IP 44
III
II
50/60 Hz
I
: 1 A or 5 A
r
IN
: 0.1 A, 1 A or 5 A
r
UN
: 110 V
r
+/- 24 V (from DC/DC-converter)
Maximum 5,5 W (without DC/DC-converter)
48-60 V DC or 110-220 V DC
Maximum voltage, 250 V AC/DC
Current carrying capacity, continuous 5 A
Green LED indicates In service
Yellow LED indicates Start
Red LED indicates Trip
Page 1