Download Print this page

ABB RXHL 422 Connection And Settings Manual page 2

Compact current relay

Advertisement

1MRK 509 057-WEN
Page 2
Indications
ServiceValues
Primary
Secondary
Settings
BasicSetting
Frequency
MainCTRatio
Phase
EarthFault
MainVTRatio
EarthFault
Functions
Group1
OverCurrent
Directional EF
Group2
OverCurrent
Directional EF
BreakerFailure
IntentOvReach
AutoReclosing
Settings
Counters
ActiveGroup
Configuration
BinaryOutputs
BinaryInputs
HMI
Display
Indications
b)
Lang/Språk
Information
Test
a)
Functions available as options
b)
English and the other available language is swedish
Binary input functions:
Block or Enable I>, I>>, I>>>, I
Reset LED´s and thermal heat counter
External start of breaker failure
Alternative setting group
Circuit-breaker closed (automatic reclosing)
Circuit-breaker ready (automatic reclosing)
Block automatic reclosing function
Binary output functions:
Start I>, I>>, I>>>, Θ>, I
Trip I>, I>>, I>>>, Θ>, I
Re-trip of breaker-failure
Back-up trip of breaker-failure
Setting group 2 active
In service
Intentional overreach trip
Automatic reclosing is activated
Automatic reclosing is ready
Automatic reclosing is started
Reclosing pulse to circuit-breaker
Unsuccessful reclosing
RXHL 422 Compact current relay
a)
a)
>, I
>> and I
>>>
->N
->N
->N
>, I
>> and I
>>>
->N
->N
->N
>, I
>> and I
>>>
->N
->N
->N
MENU TREE OF RXHL 422
Indications: The menu provides information about the recorded events.
Unfilled squares for no recorded events (since last clearing).
Filled grey squares for previous recorded event.
Filled squares for latest recorded event.
Recorded events can be cleared by press and hold down the "C" for
2 seconds.
ServiceValues: This menu provides information of operating conditions.
ServVal/Primary:
Primary system values.
ServVal/Secondary:
Secondary system values.
Settings: Under this is menu the user set basic values, operate levels, time
delays and active group.
BasSet/Freq:
Rated relay frequency.
BasSet/MainCTR:
Ratio of main CT´s.
BasSet/MainVTR:
Ratio of main VT´s.
Func/Grp1/OvCurr:
Operate levels, times, etc.
Func/Grp1/EarthFl:
Operate levels, times, etc.
Func/Grp2/OvCurr:
Operate levels, times, etc.
Func/Grp2/EarthFl:
Operate levels, times, etc.
Func/BrkFail:
Start by, operate levels, times, etc.
a)
Func/IntOvRe
:
Start by, times, etc.
a)
Func/AutoRec
:
Start by, shoots, times, etc.
ActiveGroup:
Selection of the active setting group.
Configuration: Under this is menu the user configure I/O signals.
Config/BinOut:
Function to selected binary output with
a mark.
Config/BinIn:
Binary input signal to selected function
with a mark.
HMI: Under this menu the user select the appearance of the display.
HMI/Display:
Contrast level and turn-off or not.
HMI/Indicat:
Led´s to remain or not.
Lang/Språk: In this menu the user select language, English/Svenska.
Information: In this menu the user retrieve information of the relay,
type, variant, options, etc.
Test: In this menu the user test the binary I/O signals during installation.
BinOut:
Activate selected output by pressing "E".
BinIn:
Binary input will be inverted when it´s
energized (RL voltage).
Saving dialogue: Appears when the user going upwards in the menu tree
from a menu which consist editable values.
YES:
Confirm the last setting(s) and exit.
NO:
Confirm the previous setting(s) without
any changes and exit.
CANCEL:
Returns to the last setting(s) or to the last
menu.
ABB Automation Products AB
Version: Initial version
Issue date: May 2000

Advertisement