Connection data of voltage modules:
Maximum wire cross-section:
Wire strip length without wire end ferrules:
Sleeves length (wire range) of wire end ferrules:
After attachment, the wire end ferrules must comply with the geometry for terminal cells
according to EN 60 947-7, class A1.
Select the corresponding wire end ferrules and attachment tools.
max. torque:
screw driver width:
Figure 2 Connection data of voltage modules
Insert the stripped wire into the terminal cell until stop and tighten the screw.
8
1.5 mm
0.8 Nm (7 in-lb)
3.5 mm
10 to 12 mm
2
(AWG 15); with or without wire end ferrules
10 to 12 mm
min. 10 mm
(e.g. DIN 46 228-E1,5-10).
min. 10 mm
7XT3400-0*A00/DD