Gc 3 Flame Signal Test; Transducer Usage; Gc 1 Flame Signal Test - Lennox G21Q3-40 Unit Information

Hide thumbs Also See for G21Q3-40:
Table of Contents

Advertisement

To Measure Flame Signal−GC 1 Ignition Control:
WARNING
Fire and explosion hazard.
These instructions MUST be followed exactly.
Can cause a fire or explosion resulting in property
damage, personal injury or loss of life.

GC 1 FLAME SIGNAL TEST

D.C.
MICROAMP
METER
(−)
(+)
SENSOR
WIRE
FLAME SENSOR
FIGURE 63
1 − Place meter in series between ignition control and sen
sor wire. Connect positive (+) lead of meter to ignition
control sensor connection and negative (−) lead of the
meter to sensor wire. See figure 63.
2 − Set thermostat for a heating demand and check flame
signal with unit operating. For G21/GSR21 series with
the GC 1 ignition control (A3), a reading of 3 to 5 micro
amps DC is typical. The control will operate between 1
and 5 microamps DC.
Flame signal may rise above 3 to 5 microamps for the first
few seconds after ignition and then level off.
To Measure Flame Signal−GC 3/G891 Ignition Controls:
A
transducer
(Part
#78H5401
avail
able from Lennox
Repair Parts) is re
quired to measure
flame
signal
on
GC 3
/
G891
equipped units. See figure 64. The transducer con
verts microamps to volts on a 1:1 conversion. GC 3
flame signal is 1.5−2.5 microamps, therefore a read
ing of 1.5−2.5 volts should be read on the meter. G891
flame signal is 1.2−2.2 microamps, therefore a read
ing of 1.2−2.2 volts should be read on the meter. The
transducer plugs into the meter. See figure 66 for
proper use of transducer.
1 − Set the volt meter to the DC voltage scale. Insert
transducer into the VDC and common inputs. Ob
serve correct polarities. Failure to do so results in neg
ative (−) values.
IGNITION
CONTROL
SENSE" TERMINAL
TRANSDUCER
(PART #78H5401)
FIGURE 64
2 − Turn off supply voltage to control.
3 − Disconnect flame sensor lead from terminal of ignition
control.
4 − Connect (+) lead of transducer to ignition control sen
sor connection. See figure 65.
5 − Connect (−) lead of the transducer to sensor wire. See
figure 65.
6 − Turn supply voltage on and close thermostat con
tacts to cycle system.
7 − When unit lights read voltage on meter display. Re
member 1 DC volt = 1 DC microamp. For G21/GSR21
series with the GC 3 ignition control (A3), a reading of
1.5−2.5 volts DC should occur. For G21/GSR21 series
with the G891 ignition control (A3), a reading of 1.2−2.2
volts DC should occur.

GC 3 FLAME SIGNAL TEST

TRANSDUCER
DIGITAL
METER
(+)
(−)
SENSOR
WIRE
FLAME SENSOR

TRANSDUCER USAGE

(+) TO GC 3
SENSOR
TERMINAL
Page 48
SENSE" TERMINAL
FIGURE 65
NOTE−MUST USE
DIGITAL METER
1 − Set meter to DC voltage scale.
2 − Insert transducer into the VDC and
Common inputs. Observe polarities
3 − Connect (+) end of transducer lead to
GC 3 sensor terminal.
4 − Connect (−) end to sensor wire.
SET DIAL TO MEASURE
VDC
TRANSDUCER
PART no. 78H5401
(+)
RED COLLAR
INDICATES
(−)
(−) TO
SENSOR WIRE
FIGURE 66
IGNITION
CONTROL
POSITIVE
LEAD