Concentric Termination; Concentric Wall Termination; Minimum Diameter For G21/Gsr21 Venting; Standard Intake/Exhaust Termination - Lennox G21Q3-40 Unit Information

Hide thumbs Also See for G21Q3-40:
Table of Contents

Advertisement

WARNING
After reassemble, double check all connections to
prevent exhaust products from entering living
space.
S − Concentric Termination
(Figures 55, 56 and 57 )
In concentric termination, intake and exhaust piping are
centrally located. See figures 55 and 56. See figure 57 for
a detailed cutaway.
CONCENTRIC ROOFTOP TERMINATION
EXHAUST
TERMINATION
INTAKE
TERMINATION
EXHAUST
FIGURE 55

CONCENTRIC WALL TERMINATION

EXHAUST
INTAKE
FIGURE 56
CONCENTRIC WALL TERMINATION
TOP VIEW
EXHAUST TUBE
INTAKE TUBE
EXHAUST
INTAKE
FIGURE 57
Exhaust piping must terminate straight out or up at a level 12
inches above normal snow accumulation. Termination must
not be within six feet of other vents or three feet of structure
openings. For proper vent sizes see table 14 .
12" ABOVE AVERAGE SNOW
ACCUMULATION
INTAKE
EXHAUST
TERMINATION
INTAKE
TERMINATION
(CUTAWAY)
EXHAUST
TERMINATION
SIDE VIEW
INTAKE TERMINATION

MINIMUM DIAMETER FOR G21/GSR21 VENTING

Pipe Length
(Max. Feet)
5
10
20
30
40
50
60
70
80
90
Refer to GSR21/GSR14 Exhaust/Intake Air Termination
Kits installation instructions for installation procedures
which meet local and national codes.
The exhaust line must be reduced at wall termina
tion to 1 1/2".
T − Standard Intake/Exhaust Termination
(Figures 58, 59, 60, 61 )
Intake and exhaust pipes should be placed as close to
gether as possible at termination end. MAXIMUM SEP
ARATION IS 3 IN. ON ROOF TERMINATION AND 6 IN.
ON SIDE WALL TERMINATIONS. END OF EXHAUST
PIPE MUST EXTEND AT LEAST 8 IN. PAST END OF IN
TAKE PIPE.
Intake MUST be up wind (prevailing wind) of exhaust pipe.
Both intake and exhaust MUST be in the same pressure
zone (do not exit one through the roof and one through the
side of the house). These precautions are to ensure that no
exhaust gas recirculation occurs.
Exhaust piping must terminate straight out or up and ter
mination must not be within six feet of other vents or three
feet of structure openings. For proper sizing see table 14.
Refer to G21/GSR21 operation and installation instruc
tions for detailed instruction of proper termination installa
tions which meet local and national codes.
Page 43
TABLE 14
Number of 90° Elbows
0
2
4
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2−1/2
2−1/2
2−1/2
2
2−1/2
2−1/2
2−1/2
2−1/2
2−1/2
2−1/2
2−1/2
2−1/2
3
2−1/2
3
3
IMPORTANT
6
8
2
2
2
2
2
2−1/2
2−1/2
2−1/2
2−1/2
2−1/2
2−1/2
2−1/2
2−1/2
3
3
3
3
3
3
3