Baxi LUNA SAT RCZ-MB Installation And Operating Manual page 35

Built-in user modules
Table of Contents

Advertisement

Available languages

Available languages

TABLE: HEAT DEMAND – FLOW OF WATER IN HEATING CIRCUIT
Heating domestic
water heat capacity
(kW)
7
8
9
10
11
12
13
14
15
16
17
18
19
20
ΔT = Difference between User Module Delivery – Return Temperature
TABLE: COOLING DEMAND – COOLED AREA
Area to cool
(m
)
2
60
70
80
90
100
110
120
(*) Volumetric heat load "F": 15 - 25 - 40 W/m
Height of volume to be cooled = 3 m
Δt = internal and external temperature difference (internal T = 26 °C, external T = + 34°C)
F1 = 15 W/m
buildings with an excellent insulation level and excellent solar radiation protection
3
F2 = 25 W/m
buildings with a good insulation level and good solar radiation protection
3
F3 = 40 W/m
buildings with a scarce insulation level and scarce solar radiation protection
3
TABLE: COOLING DEMAND – FLOW OF WATER IN COOLING CIRCUIT
Heating capacity
Cooling
(kW)
7
8
9
10
11
12
13
ΔT = Difference between User Module Delivery – Return Temperature
Delivery temperature: 12°C
Return temperature: 7°C
INSTALLATION AND OPERATING MANUAL
Flow rate of Heating
circuit with ΔT = 15
K (l/h)
401
459
516
573
631
688
745
803
860
917
975
1032
1089
1147
Cooling demand (*)
With F1 = 15 W/m
3
(kW)
2,7
3,2
3,6
4,1
4,5
5,0
5,4
with Δt = 8 K (fancoil heaters)
3
Capacity of cooling
circuit
With ΔT = 5 K
(l/h)
1204
1376
1548
1720
1892
2064
2236
35
Flow rate of Heating
circuit with ΔT = 20 K
(l/h)
301
344
387
430
473
516
559
602
645
688
731
774
817
860
Cooling demand (*)
With F2 = 25 W/m
3
(kW)
4,5
5,3
6,0
6,8
7,5
8,3
9,0
Cooling demand (*)
With F3 = 40 W/m
3
(kW)
6,3
7,4
8,4
9,5
10,5
11,6
12,6
7213763.01 - en