Baxi LUNA SAT RCZ-MB Installation And Operating Manual page 34

Built-in user modules
Table of Contents

Advertisement

Available languages

Available languages

HOME A
Figure 2: Floor layout
The indicative diagram in figure 2 only illustrates the feed pipes of the individual user modules.
The heating plant inside the zone controlled by the module must be realised by feeding the heating elements according
to normal methods.
- Water temperature range in centralised plant:
- Maximum water pressure in centralised plant:
- Module feed flow rate (nominal):
- Maximum recommended speed of heat transfer fluid:
- Pressure drop in module
Some purely indicative general sizing data is shown below:
TABLE: HEAT DEMAND – HEATED AREA
Area to heat
(m
)
2
60
70
80
90
100
110
120
130
140
150
(*) Volumetric heat load "F": 20 - 30 - 45 W/m
Height of volume to be heated = 3 m
Δt = internal and external temperature difference (internal T = 20 °C, external T = - 5°C)
F1 = 20 W/m
buildings with an excellent level of insulation
3
F2 = 30 W/m
buildings with an good level of insulation
3
F3 = 45 W/m
buildings with an low level of insulation
3
INSTALLATION AND OPERATING MANUAL
HOME B
3.1 GENERAL SIZING DATA
Heat demand (*)
With F1 = 20 W/m
3
(kW)
3,6
4,2
4,8
5,4
6,0
6,6
7,2
7,8
8,4
9,0
3
with Δt = 25 K;
34
HOME C
60 - 75 °C
4 bar
700 ÷ 1000 l/h
1 ÷ 1.5 m/s
20 KPa at 700 l/h (see § 6)
Heat demand (*)
With F2 = 30 W/m
3
(kW)
5,4
6,3
7,2
8,1
9
9,9
10,8
11,7
12,6
13,5
Heat demand (*)
With F3 = 45 W/m
3
(kW)
8,1
9,5
10,8
12,2
13,5
14,9
16,2
17,6
18,9
20,3
7213763.01 - en