General

Model RYY792X series of converters offer compact,
space-saving, easy installation with its plug-in structure.
Each model is modularized for a particular function. Model
RYY792X converters can be used for signal transmission
between instruments, as a controller, for monitoring, and for
various other applications.

Features

Compact, space-saving, plug-in structure.
Minimal mounting space.
Wide variety of converter types.

Specifications

Items
Power
85 V AC to 264 V AC, 50 Hz / 60 Hz
Insulation
100 M or over at 500 V DC
resistance
(Between input/output and power supply)
2000 V AC for one minute
Withstand voltage
(Between input/output and power supply)
Temperature:
Humidity:
Rated operating
conditions
Altitude:
Vibration:
Temperature:
Ambient storage &
Humidity:
transportation
conditions
Vibration:
Product
Refer to Product Specifications.
specifications

Dimensions

Refer to Figs. 1 and 2.

Accessory

Socket (See Fig. 2.)
Socket: Part No. RYY-CS3700-11P
(Though the socket is supplied with Model
Auxiliary part
RYY792X, the socket can separately be
ordered as an auxiliary part.)

CE Marking Conformity

This product must be installed in a panel cabinet. Besides,
the product in the panel cabinet must be out of reach of
unauthorized people who are not well-trained for electric
facilities.
This product complies with the following Electromagnetic
Compatibility (EMC) and the Low Voltage Directive (LVD).
EMC: EN61326-1
Class A, Table 2 (For use in an industrial
electromagnetic environment)
LVD: EN61010-1
Overvoltage category II
Pollution degree 2
Converter
Specifications
-5 C to 55 C
5 %RH to 90 %RH
(Non-condensing)
2,000m or lower
4.9 m/s², 5 Hz to 100 Hz
-10 C to 60 C
5 %RH to 90 %RH
(Non-condensing)
9.8 m/s², 0 Hz to 60 Hz
Dimensions
Potentiometer knob for SPAN adjustment
Potentiometer knob for ZERO adjustment
25
8
Main unit fixing screw
Figure 1. Dimensions (mm): With the socket assembled
7.5
4.2
Figure 2. Dimensions (mm): Socket in front
1
AB-6484
Specifications/Instructions
Socket
Main unit
33
84
4.2
Slit for wall mounting
Slit for wall mounting
(with M4 screw)
(with M4 screw)
Input/output terminals
9.5
29

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RYY792 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Azbil RYY792 Series

  • Page 1: Specifications

    AB-6484 Specifications/Instructions Converter General Model RYY792X series of converters offer compact, space-saving, easy installation with its plug-in structure. Each model is modularized for a particular function. Model RYY792X converters can be used for signal transmission between instruments, as a controller, for monitoring, and for various other applications.
  • Page 2 This product is targeted for general air conditioning. Do not use this product in a situation where human life may be affected. If this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil Corporation’s sales representative.
  • Page 3: Product Specifications

    AB-6484 Product Specifications Input signal* Output signal* Remarks Converter Application Model number Load Input type Range Range With insulation resistance resistance Ni temperature temperature detector RYY792N3001 750  or Ni/I detector (508.4 /0 C)/  RYY792N3002 4 to 20mA* 0.15%FS 0.15 With insulation 0 to 50 C converter...
  • Page 4 AB-6484 Wire Connections Wire Specifications Select the appropriate size, length, and type of wires according to the following table. Converter type Input wiring Output wiring Power line 5  or lower per wire Converters (JPt/I, Pt/I) Isolator, limiter, monitor switch, 24 V DC power 3 ...
  • Page 5 AB-6484 Adjustment Precautions for making adjustment IMPORTANT:  This product is adjusted before shipment. Do not turn the potentiometer knobs with paint locks.  When adjusting the potentiometer knobs on the front of the unit, use the appropriate size driver. Do not turn the potentiometer knobs beyond their limits.
  • Page 6 AB-6484 Potentiometer knob for ZERO adjustment Potentiometer knob for SPAN adjustment High/low limit selector Polarity indicator LED (top: high limit, bottom: low limit) Up/down control of setpoint High/low limit display Figure 7. Front panel of the limiter Ratio bias setup How to set the ratio: Switch the ratio/bias selector to the “RATIO”...
  • Page 7: Handling Precautions

    AB-6484 Handling Precautions IMPORTANT:  This is a precision device. Ensure careful handling. Any mishandling or accidental dropping will damage the product.  As the product utilizes electronic components, do not place in wet or humid locations.  The plastic housing may be deformed if being exposed to high heating temperature. ...
  • Page 8 AB-6484 Specifications are subject to change without notice. Building Systems Company http://www.azbil.com/ Rev. 5.0 Dec. 2015 AB-6484...

This manual is also suitable for:

Ryy792n3002Ryy792n3003Ryy792n3001Ryy792p3011Ryy792p3012Ryy792p3013 ... Show all

Table of Contents