Download Print this page

UE 120 Series Installation And Maintenance Instructions page 4

Explosion proof temperature controls

Advertisement

Internal Set Point Adjustment
Types C120, F120
Dimension A
Models
Inches
mm
120,121
8.84
224,0
1BS-M9B
8.19
208,0
External Set Point Adjustment
Types B121, B122, E121, E122
Dimension A
Models
Inches
mm
120,121
10
254,0
1BS-M9BB
9.31
237,0
Models 1BS-M9B
NPT
Immersion stem
Bulb & capillary
1.12
NPT
Immersion stem
Bulb & capillary
Models 120-121
RECOMMENDED PRACTICES AND WARNINGS
United Electric Controls Company recommends careful consideration
of the following factors when specifying and installing UE pressure
and temperature units. Before installing a unit, the Installation and
Maintenance instructions provided with unit must be read and
understood.
• To avoid damaging unit, proof pressure and max temperature
limits stated in literature and on nameplates must never be exceeded,
even by surges in the system. Operation of the unit up to proof pres-
sure or max temperature is acceptable on a limited basis (i.e.start-up,
testing) but continuous operation must be restricted to the designated
adjustable range. Excessive cycling at proof pressure or maximum
temperature limits could reduce sensor life.
• A back-up unit is necessary for applications where damage
to a primary unit could endanger life, limb or property. A high or low
limit switch is necessary for applications where dangerous runaway
condition could result.
• The adjustable range must be selected so that incorrect,
inadvertent or malicious setting at any range point can not result in an
unsafe system condition.
• Install unit where shock, vibration and ambient temperature
fluctuations will not damage unit or affect operation. Orient unit so
that moisture does not enter the enclosure via the electrical
connection.
• Unit must not be altered or modified after shipment. Consult UE if
modification is necessary.
• Monitor operation to observe warning signs of possible damage
to unit, such as drift in set point. Check unit immediately.
• Preventative maintenance and periodic testing is necessary for
critical applications where damage could endanger property or
personnel.
• For all applications, a factory set unit should be tested before use.
• Electrical ratings stated in literature and on nameplate must not
be exceeded. Overload on a switch can cause damage, even on the
first cycle. Wire unit according to local and national electrical codes,
using wire size recommended in installation sheet.
• Use only factory authorized replacement parts and procedures.
• Do not mount unit in ambient temp. exceeding published limits.
• For remote mounted temperature units, capillary lengths beyond
10 feet can increase chance of error, and may require re-calibration of
set point and indication.
LIMITED WARRANTY
UE warrants that the product thereby purchased is, upon delivery, free
from defects in material and workmanship and that any such product
which is found to be defective in such workmanship or material will be
repaired or replaced by UE (F.O.B. UE); provided, however, that this
warranty applies only to equipment found to be so defective within a
period of 12 months after installation by buyer but not to exceed 18
months after delivery by the seller. Except for the limited warranty
of repair and replacement stated above, UE disclaims all war-
ranties whatsoever with respect to the product, including all
implied warranties of merchantability or fitness for any
particular purpose.
LIABILITY LIMITATION
The sole and exclusive remedy of buyer for any liability or seller
for any claim, including incurred in connection with (I) breach of any
warranty whatsoever expressed or implied, (II) a breach of contract,
(III) a negligent act or acts (or negligent failure to act) committed by
seller, or (IV) an act for which strict liability will be imputed to seller,
is limited to the limited warranty or repair and replacement stated
herein. In no event shall the seller be liable for any special,
indirect, consequential or other damages of a like general nature,
including, without limitation, loss of profits or production, or
loss or expenses of any nature incurred by any third party.
U N I T E D
E L E C T R I C
C O N T R O L S
180 Dexter Ave., P.O. Box 9143, Watertown, MA 02272-9143 USA
617 926-1000 Fax 617 926-2568
IKON10M997
4

Advertisement

loading

This manual is also suitable for:

E121E122E122pB121B122C120 ... Show all