UE 120 Series Installation And Maintenance Instructions

Explosion proof temperature controls

Advertisement

Quick Links

120 Series Explosion Proof*
Temperature Controls
Remote Types E121, E122,
E122P, F120; Local Types B121,
B122, C120
FM, UL & CSA listed; Meets Divisions 1 & 2: Class 1,
Groups B, C & D; Class II, Groups E, F & G;
and Class III & Heat Trace Units
NOTE: CSA, Class I, Group B approval does not
apply to controls with option code "1530".
Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of
Recommended Practices, Liabilities and Warrantees.
GENERAL
MISUSE OR MISAPPLICATION OF THIS
PRODUCT MAY CAUSE EXPLOSION AND
PERSONAL INJURY. THESE INSTRUCTIONS
MUST BE THOROUGHLY READ AND UNDER-
STOOD BEFORE UNIT IS INSTALLED.
Temperature variations of a liquid filled sensing bulb
are hydraulically transmitted to a bellows or
diaphragm which either actuates or deactuates one
or two snap-acting switches at a predetermined set
point(s). Set points are adjusted by turning an exter-
nal calibrated knob and pointer (B, E types) or inter-
nal adjustment screw (C, F types).
MAXIMUM TEMPERATURE: THE HIGHEST
TEMPERATURE TO WHICH A SENSING ELE-
MENT MAY BE OCCASIONALLY OPERATED
WITHOUT ADVERSELY AFFECTING SET POINT
CALIBRATION AND REPEATABILITY. MAXIMUM
TEMPERATURE STATED IN LITERATURE AND ON
NAMEPLATE MUST NEVER BE EXCEEDED, EVEN
BY SURGES IN THE SYSTEM. OCCASIONAL
OPERATION
TEMPERATURE IS ACCEPTABLE (E.G. START-
UP, TESTING).
SHOULD BE RESTRICTED TO THE DESIGNATED
ADJUSTABLE RANGE.
Part I - Installation
MOUNTING
INSTALL UNIT WHERE SHOCK, VIBRATION
AND TEMPERATURE FLUCTUATIONS ARE
MINIMAL. ORIENT UNIT SO THAT MOISTURE IS
PREVENTED FROM ENTERING THE ENCLO-
SURE. IT IS IMPERATIVE THAT PROPERLY
RATED EXPLOSION-PROOF SEALING FITTINGS
BE USED FOR ELECTRICAL WIRE ENTRY. DO
NOT MOUNT UNIT IN AMBIENT TEMPERATURES
EXCEEDING PUBLISHED LIMITS.
ALWAYS HOLD A WRENCH ON THE
CONNECTION HEX WHEN INSTALLING
LOCAL MOUNTED UNITS. DO NOT TIGHTEN BY
* Enclosures are designed to withstand gas vapor explosions without bursting or loosen-
ing of joints, and are capable of arresting the propagation of flame from the interior of the
enclosure to the surrounding atmosphere.
OF
UNIT
UP
TO
CONTINUOUS OPERATION
TOOLS NEEDED
Screwdriver
Adjustable Wrench to 1 1/2"
TURNING ENCLOSURE. THIS WILL DAMAGE
SENSOR AND WEAKEN SOLDER OR WELDED
JOINTS.
120 Series remote mounted temperature controls
should be mounted vertically (temperature assembly
facing down) or horizontally (electrical conduit facing
up) Controls may be surface mounted via the 4-1/4"
screw clearance holes on the enclosure or through
the use of a mounting bracket (See Mounting
Dimensions).
Breather Drain Option M450: Types C120, F120
(Not available on FM approved units)
Mount with breather drain facing down and conduit
connection facing up (See Figure I). The conduit
connection must be properly sealed (potted) for this
type of installation.
Breather Drain Option M450: Types B121,
B122, E121 & E122
(Not available on FM approved units)
Mount in vertical position with temperature assembly
MAX.
and breather drain facing down (See Figure 2).
Potted
Conduit
Connection
Figure 1: Types C120, F120
Figure 2: Types B121, B122, E121, E122
U N I T E D
E L E C T R I C
C O N T R O L S
Installation and Maintenance
Instructions
Breather Drain
(facing down)
Breather Drain
(facing down)
IMT120-03
1

Advertisement

loading

Summary of Contents for UE 120 Series

  • Page 1 SENSOR AND WEAKEN SOLDER OR WELDED JOINTS. MISUSE OR MISAPPLICATION OF THIS PRODUCT MAY CAUSE EXPLOSION AND 120 Series remote mounted temperature controls PERSONAL INJURY. THESE INSTRUCTIONS should be mounted vertically (temperature assembly MUST BE THOROUGHLY READ AND UNDER- facing down) or horizontally (electrical conduit facing STOOD BEFORE UNIT IS INSTALLED.
  • Page 2 WIRING Part II - Adjustments TOOLS NEEDED DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING UNIT. WIRE UNITS 3/16” Open End Wrench ACCORDING TO NATIONAL AND LOCAL ELECTRI- 1/4” Open End Wrench CAL CODES. MAXIMUM RECOMMENDED WIRE 1/4” Allen Wrench SIZE IS 14 AWG. THE RECOMMENDED TIGHTEN- TORQUE FIELD WIRING...
  • Page 3 Type E122P (Dual Switch Models) ONLY FACTORY AUTHORIZED REPLACEMENT PARTS AND PROCEDURES. Remove cover, unscrew and remove COMPONENTS FOR REPLACEMENT PARTS terminal blocks and insulator, letting INCLUDE THE SWITCHES AND THE THERMAL terminal blocks hang. ASSEMBLIES ONLY. ORDER PARTS BY NAME Unscrew terminal block supports PLATE INFORMATION ON MODEL, RANGE AND and remove (2) switch mounting screws...
  • Page 4 Orient unit so that moisture does not enter the enclosure via the electrical connection. Dimension A • Unit must not be altered or modified after shipment. Consult UE if Models Inches modification is necessary.