Control Drawings - Banner Sure Cross DX99 Quick Start Manual

Flexpower thermocouple node (metal housing)
Table of Contents

Advertisement

Thermocouple Type
Use DIP switches 5, 6, 7, and 8 to select the thermocouple type. The default position is the OFF position for all switches, setting the
thermocouple to a J-type thermocouple.
Supported Thermocouple Types
The thermocouple Node is configured, by default, to use J-type thermocouples. The following thermocouples are available by
configuring the Node.
Thermocouple
Type B
Type C
Type E
Type J
Type K
Type L
Type N
Type R
Type S
Type T
Type U
Terminal Blocks and Wiring
The complete control drawing is document
The GND connection can be considered the same as the housing ground when using a stainless steel antenna feedthrough (model BWA-
HW-016 or BWA-HW-017). When the stainless steel antenna feedthroughs are not used, the GND connection is isolated from the metal
housing.

Control Drawings

4
141513
at www.bannerengineering.com.
Ax+ and Ax–. Analog IN x. Analog inputs for devices requiring more than one
connection, such as thermocouples or RTDs. When there is no Ax–, use Ax+ as an
analog input.
GND
DI2
DIx. Discrete IN x
GND
GND. Ground/dc common connection
DI1
A6
A5
A4+
A4−
A3+
A3−
A2+
A2−
A1+
A1−
www.bannerengineering.com - Tel: +1-763-544-3164
Sure Cross
Range °F
212 to 3,272 °F
32 to 4,208 °F
-58 to 1,832 °F
-292 to 1,382 °F
-292 to 2,282 °F
-328 to 1,652 °F
32 to 2,192 °F
32 to 2,912 °F
32 to 2,642 °F
-238 to 752 °F
-148 to 1,112 °F
®
DX99 FlexPower Thermocouple Node (Metal Housing)
Range °C
100 to 1,800 °C
0 to 2,320 °C
-50 to 1,000 °C
-180 to 750 °C
-180 to 1,250 °C
-200 to 900 °C
0 to 1,200 °C
0 to 1,600 °C
0 to 1,450 °C
-150 to 400 °C
-100 to 600 °C
P/N 142681 Rev. O