7.10 Dual-channel Safety Door Monitoring with Proximity Sensors,
Automatic Reset and Emergency Stop
Achievable safety rating
Stop category
Features
Safety sensor/operating
mechanism
Notes
Note: All example applications shown are proposals without warranty. In any case the operator has
to perform a safety review of the entire site.
If the emergency stop button is pushed or at least one magnetic switch is opened, the EP-19xx
switches off the 24-V supply for the modules within safety segment and thus also contactors K3 and
K4. The failure of a switching element in the emergency stop button or a cross-circuit in its supply
lines does not result in the failure of the emergency stop mechanism and is detected within the fault-
reaction time.
The EP-19xx switches on the 24-V supply for modules within the safety segment if:
Emergency button is unlocked
Both magnetic contacts are closed
Feedback circuit (NC contacts of K3 and K4) is closed
Contactors K3 and K4 are controlled by the PLC and can switch on as soon as the EP-19xx has
switched on the 24-V supply. To reset the system, press the reset button within 0.1 to 2 s after
switching on the power supply, even when automatic reset is used.
GFK-2956A
Cat. 4
DIN EN ISO 13849-1
PLe
DIN EN ISO 13849-1
SIL3
IEC 62061/61508
0
EN 60204-1
• Dual-channel monitoring
• Cross-connection detection
• Automatic reset
• Monitoring of external contactors (EDM)
• Emergency stop button
• 2 proximity switches
• The power supply for the proximity
switches is not shown
• The application must be compatible
with the automatic start-up function
November 2017
Chapter 7. Example Applications
59